EK-DI-163AC10-A08 C
15.70 kW
Defrost: None
Product code: EK-DI-163AC10-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 19,071 m³/h |
|---|---|
| External surface | 52.9 m² |
| Inner volume | 22.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 199 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EK-DI-163AC10-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.30 | 6.10 | 5.97 | 5.90 | 5.83 | 5.76 | 5.70 | 5.68 | 6.01 | 6.48 | 6.32 | 6.26 | 6.18 | 6.06 |
| 5 | 7.72 | 7.53 | 7.41 | 8.15 | 8.05 | 7.95 | 7.84 | 7.80 | 8.24 | 8.87 | 8.61 | 8.52 | 8.38 | 8.19 |
| 6 | 9.86 | 9.69 | 9.60 | 10.61 | 10.52 | 10.39 | 10.26 | 10.18 | 10.75 | 11.56 | 11.20 | 11.07 | 10.88 | 10.60 |
| 7 | 11.97 | 11.91 | 11.89 | 13.22 | 13.15 | 13.03 | 12.89 | 12.79 | 13.50 | 14.52 | 14.05 | 13.88 | 13.62 | 13.24 |
| 8 | 14.01 | 14.09 | 14.19 | 15.88 | 15.88 | 15.80 | 15.67 | 15.57 | 16.44 | 17.70 | 17.13 | 16.91 | 16.59 | 16.10 |
| 9 | 17.75 | 18.03 | 18.25 | 18.51 | 18.61 | 18.60 | 18.52 | 18.44 | 19.49 | 21.01 | 20.36 | 20.10 | 19.73 | 19.14 |
| 10 | 19.64 | 20.11 | 20.59 | 21.04 | 21.34 | 21.45 | 21.42 | 21.39 | 22.63 | 24.43 | 23.71 | 23.43 | 23.01 | 22.34 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.59 | 5.42 | 5.32 | 5.27 | 5.22 | 5.18 | 5.14 | 5.15 | 5.45 | 5.89 | 5.76 | 5.71 | 5.64 | 5.55 |
| 5 | 6.80 | 6.62 | 6.52 | 7.18 | 7.11 | 7.03 | 6.96 | 6.95 | 7.36 | 7.95 | 7.74 | 7.66 | 7.55 | 7.39 |
| 6 | 8.63 | 8.48 | 8.39 | 9.27 | 9.19 | 9.09 | 8.99 | 8.96 | 9.47 | 10.21 | 9.91 | 9.80 | 9.65 | 9.43 |
| 7 | 10.51 | 10.39 | 10.34 | 11.47 | 11.41 | 11.31 | 11.19 | 11.14 | 11.77 | 12.68 | 12.28 | 12.14 | 11.93 | 11.62 |
| 8 | 12.33 | 12.30 | 12.33 | 13.75 | 13.72 | 13.63 | 13.51 | 13.45 | 14.21 | 15.31 | 14.83 | 14.65 | 14.39 | 13.98 |
| 9 | 15.66 | 15.77 | 15.90 | 16.05 | 16.08 | 16.03 | 15.93 | 15.86 | 16.76 | 18.07 | 17.51 | 17.29 | 16.98 | 16.49 |
| 10 | 17.54 | 17.81 | 18.04 | 18.30 | 18.42 | 18.44 | 18.37 | 18.33 | 19.38 | 20.92 | 20.30 | 20.05 | 19.69 | 19.12 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 23.714 | 20.295 |
| SC2 | 0 | 8 | 15.568 | 13.448 |
| SC3 | -18 | 7 | 13.203 | 11.450 |
| SC4 | -25 | 6 | 9.601 | 8.386 |
| SC5 | -34 | 6 | 9.835 | 8.607 |
| A | 1725 mm |
|---|---|
| B | 900 mm |
| C | 1150 mm |
| F | 860 mm |
| G | 1440 mm |
| E | 1335 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 1725 mm |
|---|---|
| Width | 1440 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.