EK-SR-191DG4-A03 C
68.29 kW
Defrost: None
Product code: EK-SR-291BE7-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 50,381 m³/h |
|---|---|
| External surface | 263.6 m² |
| Inner volume | 80.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 734 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 93.9 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EK-SR-291BE7-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 25.84 | 25.45 | 25.25 | 25.17 | 25.00 | 24.79 | 24.55 | 24.95 | 26.41 | 28.55 | 27.89 | 27.65 | 27.32 | 26.83 |
| 5 | 31.07 | 30.94 | 30.85 | 34.33 | 34.16 | 33.86 | 33.45 | 33.90 | 35.98 | 38.90 | 37.93 | 37.60 | 37.08 | 36.29 |
| 6 | 38.73 | 39.09 | 39.43 | 44.16 | 44.13 | 43.83 | 43.30 | 43.68 | 46.30 | 49.99 | 48.54 | 48.04 | 47.33 | 46.26 |
| 7 | 46.07 | 47.11 | 47.83 | 54.01 | 54.33 | 54.21 | 53.73 | 54.09 | 57.29 | 61.84 | 59.91 | 59.20 | 58.17 | 56.59 |
| 8 | 52.48 | 54.16 | 55.74 | 63.53 | 64.51 | 64.90 | 64.57 | 64.96 | 68.80 | 74.33 | 72.01 | 71.10 | 69.77 | 67.63 |
| 9 | 64.77 | 67.45 | 69.91 | 72.10 | 73.48 | 74.24 | 74.44 | 75.19 | 79.80 | 86.56 | 84.36 | 83.46 | 81.86 | 79.24 |
| 10 | 70.80 | 74.40 | 77.67 | 80.54 | 82.41 | 83.49 | 83.90 | 84.75 | 89.94 | 97.55 | 95.09 | 94.06 | 92.52 | 89.97 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 21.98 | 21.60 | 21.43 | 21.41 | 21.30 | 21.15 | 20.97 | 21.63 | 22.93 | 24.84 | 24.35 | 24.16 | 23.91 | 23.53 |
| 5 | 26.16 | 25.92 | 25.86 | 28.75 | 28.59 | 28.35 | 28.01 | 28.64 | 30.48 | 33.01 | 32.26 | 32.01 | 31.66 | 31.17 |
| 6 | 32.72 | 32.70 | 32.82 | 36.58 | 36.46 | 36.17 | 35.70 | 36.24 | 38.47 | 41.59 | 40.41 | 40.01 | 39.45 | 38.64 |
| 7 | 39.05 | 39.43 | 39.88 | 44.74 | 44.74 | 44.46 | 43.90 | 44.29 | 46.93 | 50.69 | 49.06 | 48.46 | 47.60 | 46.27 |
| 8 | 45.13 | 46.04 | 46.93 | 52.82 | 53.08 | 52.93 | 52.40 | 52.72 | 55.80 | 60.26 | 58.19 | 57.39 | 56.22 | 54.35 |
| 9 | 56.45 | 57.93 | 59.51 | 60.94 | 61.53 | 61.59 | 61.13 | 61.42 | 64.99 | 70.20 | 67.79 | 66.81 | 65.36 | 62.98 |
| 10 | 61.80 | 64.12 | 66.25 | 68.15 | 69.30 | 69.72 | 69.70 | 70.31 | 74.39 | 80.34 | 77.67 | 76.51 | 74.80 | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 95.088 | 77.665 |
| SC2 | 0 | 8 | 64.959 | 52.717 |
| SC3 | -18 | 7 | 54.200 | 44.763 |
| SC4 | -25 | 6 | 39.432 | 32.821 |
| SC5 | -34 | 6 | 38.864 | 32.754 |
| A | 3060 mm |
|---|---|
| B | 1360 mm |
| C | 2790 mm |
| F | 1310 mm |
| G | 1770 mm |
| E | 2665 mm |
| H | 1393 mm |
| I | 3090 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 3060 mm |
|---|---|
| Width | 1393 mm |
| Height | 2790 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.