EK-SR-280BG7-A05 C
76.66 kW
Defrost: None
Product code: EK-SR-291DE10-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 60,583 m³/h |
|---|---|
| External surface | 285.7 m² |
| Inner volume | 117.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 896 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EK-SR-291DE10-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 29.28 | 29.07 | 28.98 | 28.97 | 28.81 | 28.57 | 28.28 | 28.44 | 30.06 | 32.43 | 31.56 | 31.23 | 30.77 | 30.09 |
| 5 | 34.77 | 34.98 | 35.23 | 39.34 | 39.34 | 39.12 | 38.77 | 38.89 | 41.18 | 44.44 | 43.19 | 42.73 | 42.09 | 41.12 |
| 6 | 42.75 | 43.64 | 44.45 | 50.16 | 50.47 | 50.42 | 50.08 | 50.20 | 53.15 | 57.36 | 55.68 | 55.05 | 54.11 | 52.71 |
| 7 | 50.24 | 51.98 | 53.28 | 60.67 | 61.50 | 61.81 | 61.73 | 61.95 | 65.62 | 70.91 | 68.85 | 68.06 | 66.90 | 65.02 |
| 8 | 56.71 | 59.34 | 61.67 | 70.85 | 72.42 | 73.36 | 73.59 | 74.01 | 78.45 | 84.91 | 82.62 | 81.69 | 80.29 | 77.99 |
| 9 | 69.68 | 73.47 | 76.94 | 80.03 | 82.17 | 83.56 | 84.37 | 85.24 | 90.55 | 98.33 | 96.21 | 95.32 | 93.95 | 91.29 |
| 10 | 75.71 | 80.57 | 85.03 | 88.97 | 91.78 | 93.65 | 94.80 | 95.90 | 101.90 | 110.70 | 108.41 | 107.41 | 105.89 | 103.30 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 25.25 | 24.94 | 24.81 | 24.79 | 24.67 | 24.50 | 24.29 | 24.55 | 26.04 | 28.14 | 27.47 | 27.22 | 26.86 | 26.33 |
| 5 | 29.81 | 29.78 | 29.85 | 33.32 | 33.27 | 33.08 | 32.79 | 32.99 | 34.97 | 37.79 | 36.79 | 36.44 | 35.95 | 35.20 |
| 6 | 36.92 | 37.27 | 37.66 | 42.27 | 42.34 | 42.22 | 41.92 | 42.08 | 44.56 | 48.14 | 46.75 | 46.24 | 45.51 | 44.38 |
| 7 | 43.62 | 44.53 | 45.39 | 51.30 | 51.70 | 51.74 | 51.49 | 51.62 | 54.66 | 59.06 | 57.32 | 56.61 | 55.62 | 54.04 |
| 8 | 49.92 | 51.53 | 52.99 | 60.07 | 60.89 | 61.22 | 61.14 | 61.38 | 65.01 | 70.31 | 68.23 | 67.40 | 66.18 | 64.19 |
| 9 | 62.01 | 64.31 | 66.66 | 68.80 | 70.12 | 70.81 | 70.96 | 71.34 | 75.59 | 81.79 | 79.51 | 78.56 | 77.13 | 74.75 |
| 10 | 67.47 | 70.80 | 73.88 | 76.64 | 78.48 | 79.68 | 80.33 | 81.12 | 86.12 | 93.38 | 90.93 | 89.86 | 88.26 | 85.54 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 108.405 | 90.934 |
| SC2 | 0 | 8 | 74.012 | 61.382 |
| SC3 | -18 | 7 | 61.071 | 51.509 |
| SC4 | -25 | 6 | 44.448 | 37.655 |
| SC5 | -34 | 6 | 43.000 | 37.047 |
| A | 3060 mm |
|---|---|
| B | 1360 mm |
| C | 3390 mm |
| F | 1310 mm |
| G | 2370 mm |
| E | 2665 mm |
| H | 1393 mm |
| I | 3090 mm |
| D IN | 2 x Ø28 |
| D OUT | 2 x Ø54 |
| Length | 3060 mm |
|---|---|
| Width | 1393 mm |
| Height | 3390 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.