Skip to Content

Blast freezer EK-SR-380CC4-A05 C

Blast freezer EK-SR-380CC4-A05 C
Illustrative photo

Producer: Karyer · Line: EK-SR (Blast Freezers)

Product code: EK-SR-380CC4-A05 C

Cooling capacity i
100.69 kW
Air flow
77,919 m³/h
Fin spacing
4.6 mm
Fans
3 × ⌀800 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EK-SR — EK-SR - blast freezer
  • B
    Number of fans: 3 — Number of fans (one digit).
  • C
    Fan diameter: 80 — Ø800 mm
  • D
    Dimensional data - coil size letter: C — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: C — 4 tube rows
  • F
    Fin spacing: 4 — Fin spacing about 4 mm
  • G
    Generation code: A — Generation A
  • H
    Fan data: 05 — Ø800: 400V/3Ph/50Hz, 4-pole

Data

Evaporator
Air flow 77,919 m³/h
External surface 488.7 m²
Inner volume 97.8 dm³
Fin spacing 4.6 mm
Fin materialAluminium
Net weight 1,034 kg
Fans
Quantity 3
Diameter 800 mm
Speed 1,310 rpm
Power 11,700 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 73.0 dB(A)
Sound power 98.0 dB(A)
Energy class E
Connections
Inlet Ø28
Outlet Ø54
Defrost
EK-SR-380CC4-A05 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
96.840 kW
Low speed (Y)
85.746 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 38.40 38.12 38.04 38.12 38.06 37.92 37.77 37.98 40.23 43.55 42.63 42.29 41.81 41.12
5 45.75 45.98 46.27 51.75 51.76 51.53 51.24 51.38 54.44 58.86 57.44 56.93 56.21 55.10
6 56.58 57.74 58.52 66.01 66.42 66.41 66.14 66.23 70.15 75.78 73.77 73.04 72.00 70.42
7 66.00 68.11 70.09 79.91 81.23 82.04 82.05 82.24 87.10 94.14 91.63 90.66 89.27 87.09
8 74.44 77.60 80.48 92.29 94.18 95.39 96.06 96.84 102.83 111.58 109.27 108.36 107.02 104.84
9 91.44 96.28 100.65 104.50 107.13 108.82 109.82 110.80 117.67 127.73 125.10 124.04 122.46 119.88
10 99.49 105.78 111.48 116.46 119.96 122.25 123.67 124.92 132.71 144.12 141.22 140.02 138.22 135.24

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 34.51 34.16 34.06 34.14 34.12 34.05 33.96 34.31 36.38 39.43 38.67 38.39 37.99 37.41
5 40.96 40.92 41.03 45.76 45.78 45.65 45.43 45.70 48.47 52.47 51.30 50.88 50.30 49.43
6 50.71 51.29 51.88 58.28 58.48 58.38 58.10 58.26 61.68 66.69 65.02 64.41 63.54 62.22
7 60.09 61.27 62.60 70.85 71.49 71.66 71.47 71.66 75.91 82.07 79.88 79.06 77.85 75.99
8 67.99 70.24 72.36 82.58 84.01 84.89 85.34 85.75 90.85 98.28 95.67 94.65 93.16 90.79
9 83.78 87.35 90.61 93.56 95.51 96.75 97.42 98.23 104.28 113.18 110.76 109.79 108.35 105.99
10 91.47 96.23 100.56 104.37 106.98 108.65 109.61 110.58 117.42 127.45 124.76 123.65 121.99 119.23

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 141.217124.763
SC2 0 8 96.84085.746
SC3 -18 7 80.50871.174
SC4 -25 6 58.51551.876
SC5 -34 6 56.91150.907

Dimensions

Dimension drawing of EK-SR-380CC4-A05 C
Dimension drawing
Dimensions as drawn
A 4360 mm
B 1360 mm
C 3090 mm
F 1310 mm
G 2070 mm
E 3965 mm
H 1393 mm
I 4390 mm
D IN 2 x Ø28
D OUT 2 x Ø54
Overall [mm]
Length 4360 mm
Width 1393 mm
Height 3090 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.