EK-SR-391CC7-A04 C
84.89 kW
Defrost: None
Product code: EK-SR-480BC7-A05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 102,445 m³/h |
|---|---|
| External surface | 351.5 m² |
| Inner volume | 105.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 1,125 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 1,310 rpm |
| Power | 15,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 74.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EK-SR-480BC7-A05 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 31.51 | 31.39 | 31.48 | 31.58 | 31.49 | 31.29 | 31.03 | 31.05 | 32.82 | 35.42 | 34.49 | 34.15 | 33.67 | 32.95 |
| 5 | 37.25 | 37.96 | 38.56 | 43.39 | 43.53 | 43.40 | 43.07 | 43.16 | 45.69 | 49.27 | 47.89 | 47.37 | 46.63 | 45.47 |
| 6 | 45.65 | 47.07 | 48.53 | 55.27 | 55.99 | 56.24 | 56.14 | 56.34 | 59.68 | 64.46 | 62.70 | 62.01 | 61.06 | 59.59 |
| 7 | 52.73 | 55.26 | ≈ 57.57 | ≈ 66.26 | 67.81 | 68.81 | 69.41 | 70.15 | 74.48 | 80.60 | 78.55 | 77.75 | 76.56 | 74.67 |
| 8 | 59.06 | 62.60 | ≈ 65.82 | ≈ 76.29 | 78.51 | 79.98 | 80.91 | 81.86 | 87.02 | 94.55 | 92.74 | 92.01 | 90.92 | 89.12 |
| 9 | 72.07 | 77.21 | 81.91 | 86.07 | 89.06 | 91.12 | 92.45 | 93.69 | 99.65 | 108.36 | 106.37 | 105.56 | 104.31 | 102.23 |
| 10 | ≈ 77.91 | 84.33 | 90.27 | 95.53 | 99.40 | 102.16 | 103.98 | 105.57 | 112.35 | 122.29 | 120.18 | 119.28 | 117.91 | 115.57 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 28.50 | 28.40 | 28.40 | 28.47 | 28.39 | 28.24 | 28.05 | 28.19 | 29.83 | 32.24 | 31.46 | 31.17 | 30.77 | 30.17 |
| 5 | 33.86 | 34.23 | 34.58 | 38.79 | 38.80 | 38.67 | 38.42 | 38.60 | 40.90 | 44.19 | 43.06 | 42.63 | 42.01 | 41.07 |
| 6 | 41.65 | 42.77 | 43.75 | 49.53 | 49.79 | 49.87 | 49.70 | 49.92 | 52.87 | 57.12 | 55.60 | 55.03 | 54.22 | 52.97 |
| 7 | 48.93 | 50.68 | 52.46 | 60.00 | 61.01 | 61.48 | 61.54 | 61.89 | 65.61 | 70.96 | 69.09 | 68.37 | 67.31 | 65.62 |
| 8 | 54.84 | 57.58 | ≈ 60.09 | ≈ 69.26 | 70.96 | 72.08 | 72.73 | 73.54 | 78.15 | 84.88 | 83.19 | 82.38 | 81.13 | 79.11 |
| 9 | 67.15 | 71.23 | 74.95 | 78.24 | 80.56 | 82.11 | 83.07 | 84.08 | 89.37 | 97.13 | 95.23 | 94.45 | 93.28 | 91.33 |
| 10 | 72.85 | 78.04 | 82.79 | 86.99 | 90.01 | 92.09 | 93.41 | 94.68 | 100.68 | 109.50 | 107.44 | 106.56 | 105.25 | 103.02 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 120.179 | 107.436 |
| SC2 | 0 | 8 | 81.862 | 73.540 |
| SC3 | -18 | 7 | 66.952 | 60.474 |
| SC4 | -25 | 6 | 48.527 | 43.752 |
| SC5 | -34 | 6 | 46.081 | 41.956 |
| A | 5660 mm |
|---|---|
| B | 1360 mm |
| C | 2790 mm |
| F | 1310 mm |
| G | 1770 mm |
| E | 5265 mm |
| H | 1393 mm |
| I | 5690 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 5660 mm |
|---|---|
| Width | 1393 mm |
| Height | 2790 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.