EK-SR-391DE7-A04 C
124.41 kW
Defrost: None
Product code: EK-SR-491BE7-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 100,791 m³/h |
|---|---|
| External surface | 527.3 m² |
| Inner volume | 154.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 1,216 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 96.9 dB(A) |
| Energy class | E |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EK-SR-491BE7-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 47.13 | 47.08 | 47.32 | 47.57 | 47.47 | 47.17 | 46.73 | 47.53 | 50.29 | 54.33 | 52.98 | 52.49 | 51.78 | 50.74 |
| 5 | 55.39 | 56.52 | 57.50 | 64.77 | 65.01 | 64.77 | 64.13 | 65.10 | 69.14 | 74.78 | 72.89 | 72.24 | 71.29 | 69.68 |
| 6 | 67.62 | 70.18 | 71.97 | 81.98 | 83.00 | 83.24 | 82.82 | 83.87 | 89.01 | 96.25 | 93.60 | 92.61 | 91.24 | 89.16 |
| 7 | 78.06 | 81.84 | ≈ 85.29 | ≈ 98.14 | 100.34 | 101.62 | 102.12 | 103.51 | 109.86 | 118.95 | 115.70 | 114.44 | 112.58 | 109.61 |
| 8 | 87.38 | 92.62 | ≈ 97.39 | ≈ 112.84 | 115.99 | 117.90 | 118.80 | 120.59 | 128.19 | 139.27 | 136.19 | 134.95 | 133.07 | 129.97 |
| 9 | 106.56 | 114.15 | 121.08 | 127.16 | 131.42 | 134.13 | 135.54 | 137.64 | 146.33 | 159.07 | 155.53 | 154.06 | 151.83 | 148.08 |
| 10 | ≈ 115.15 | 124.59 | 133.34 | 141.02 | 146.54 | 150.22 | 152.26 | 154.75 | 164.57 | 178.99 | 175.11 | 173.43 | 170.87 | 166.50 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 40.25 | 40.13 | 40.18 | 40.35 | 40.24 | 40.00 | 39.63 | 40.91 | 43.34 | 46.91 | 45.89 | 45.52 | 44.99 | 44.19 |
| 5 | 47.52 | 47.95 | 48.44 | 54.21 | 54.23 | 53.94 | 53.37 | 54.61 | 58.12 | 62.97 | 61.47 | 60.96 | 60.26 | 59.24 |
| 6 | 58.32 | 59.65 | 60.89 | 68.78 | 69.12 | 68.94 | 68.23 | 69.36 | 73.64 | 79.60 | 77.35 | 76.56 | 75.43 | 73.75 |
| 7 | 68.49 | 70.98 | 72.87 | 83.01 | 83.99 | 84.19 | 83.66 | 84.67 | 89.79 | 97.14 | 94.16 | 92.99 | 91.32 | 88.66 |
| 8 | 77.33 | 80.83 | 84.10 | 96.61 | 98.53 | 99.58 | 99.50 | 100.59 | 106.65 | 115.47 | 111.89 | 110.47 | 108.33 | 104.85 |
| 9 | 94.83 | 100.13 | 104.92 | 109.09 | 111.75 | 113.28 | 113.76 | 115.25 | 122.37 | 132.84 | 129.40 | 127.95 | 125.77 | 121.49 |
| 10 | 103.02 | 109.80 | 115.94 | 121.28 | 124.90 | 126.85 | 127.72 | 129.44 | 137.42 | 149.11 | 145.34 | 143.65 | 141.12 | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 175.113 | 145.336 |
| SC2 | 0 | 8 | 120.587 | 100.585 |
| SC3 | -18 | 7 | 99.146 | 83.470 |
| SC4 | -25 | 6 | 71.967 | 60.892 |
| SC5 | -34 | 6 | 68.264 | 58.687 |
| A | 5660 mm |
|---|---|
| B | 1360 mm |
| C | 2790 mm |
| F | 1310 mm |
| G | 1770 mm |
| E | 5265 mm |
| H | 1393 mm |
| I | 5690 mm |
| D IN | 2 x Ø35 |
| D OUT | 2 x Ø54 |
| Length | 5660 mm |
|---|---|
| Width | 1393 mm |
| Height | 2790 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.