- Catalogue
- CO₂ DX evaporators
- EB-DC (Economical)
- EB-DC-130BE4-A01 C
CO2 evaporator EB-DC-130BE4-A01 C
Defrost: None
Product code: EB-DC-130BE4-A01 C
- Fin spacing
- 4.2 mm
- Fans
- 1 × ⌀300 mm
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
Model nomenclature
How to read the code of this model.
-
A
Model code (series): EB-DC — EB-DC - economical CO₂ (R744) DX unit cooler, max. 60 barg
-
B
Number of fans: 1 — Number of fans (one digit).
-
C
Fan diameter: 30 — Ø300 mm
-
D
Dimensional data - coil size letter: B — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
-
E
Dimensional data - tube rows: E — 6 tube rows
-
F
Fin spacing: 4 — Fin spacing about 4 mm
-
G
Generation code: A — Generation A
-
H
Fan data: 01 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole
Data
| External surface | 14.8 m² |
|---|---|
| Inner volume | 2.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 24 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 64.9 dB(A) |
| Energy class | B |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø9,52 |
| EB-DC-130BE4-A01 C | None |
|---|
Performance
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R744, dew point -8 °C, air inlet 0 °C (TD 8 K)
- Single phase
- 2.593 kW
Capacity matrix [kW]
R744, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
Single phase
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.09 | 1.11 | 1.14 | 1.18 | 1.21 | 1.23 | 1.25 | 1.29 | 1.38 | 1.51 | 1.50 | 1.50 | 1.49 | 1.49 |
| 5 | 1.35 | 1.38 | 1.43 | 1.48 | 1.52 | 1.55 | 1.57 | 1.62 | 1.73 | 1.89 | 1.87 | 1.86 | 1.85 | 1.83 |
| 6 | 1.58 | 1.64 | 1.70 | 1.77 | 1.82 | 1.86 | 1.90 | 1.94 | 2.08 | 2.27 | 2.25 | 2.23 | 2.21 | 2.18 |
| 7 | 1.81 | 1.88 | 1.96 | 2.05 | 2.12 | 2.17 | 2.21 | 2.27 | 2.42 | 2.65 | 2.62 | 2.60 | 2.58 | 2.53 |
| 8 | 2.02 | 2.11 | 2.21 | 2.32 | 2.41 | 2.48 | 2.53 | 2.59 | 2.77 | 3.02 | 2.99 | 2.97 | 2.94 | 2.88 |
| 9 | 2.22 | 2.33 | 2.45 | 2.58 | 2.69 | 2.77 | 2.84 | 2.91 | 3.11 | 3.40 | 3.36 | 3.34 | 3.31 | 3.24 |
| 10 | 2.40 | 2.54 | 2.68 | 2.83 | 2.96 | 3.07 | 3.15 | 3.23 | 3.45 | 3.77 | 3.73 | 3.71 | 3.67 | 3.59 |
Standard ratings (EN 328 / Eurovent)
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.734 |
| SC2 | 0 | 8 | 2.593 |
| SC3 | -18 | 7 | 2.076 |
| SC4 | -25 | 6 | 1.698 |
| SC5 | -34 | 6 | 1.596 |
Dimensions
| A | 882 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E | 535 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø9,52 |
| Length | 882 mm |
|---|---|
| Width | 520 mm |
| Height | 415 mm |
Downloads
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.