- Catalogue
- CO₂ DX evaporators
- EB-DC (Economical)
- EB-DC-245AE7-A01 C
CO2 evaporator EB-DC-245AE7-A01 C
Defrost: None
Product code: EB-DC-245AE7-A01 C
- Fin spacing
- 7.0 mm
- Fans
- 2 × ⌀450 mm
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
Model nomenclature
How to read the code of this model.
-
A
Model code (series): EB-DC — EB-DC - economical CO₂ (R744) DX unit cooler, max. 60 barg
-
B
Number of fans: 2 — Number of fans (one digit).
-
C
Fan diameter: 45 — Ø450 mm
-
D
Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
-
E
Dimensional data - tube rows: E — 6 tube rows
-
F
Fin spacing: 7 — Fin spacing about 7 mm
-
G
Generation code: A — Generation A
-
H
Fan data: 01 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole
Data
| External surface | 36.1 m² |
|---|---|
| Inner volume | 8.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 82 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EB-DC-245AE7-A01 C | None |
|---|
Performance
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R744, dew point -8 °C, air inlet 0 °C (TD 8 K)
- Single phase
- 12.687 kW
Capacity matrix [kW]
R744, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
Single phase
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.21 | 5.31 | 5.45 | 5.63 | 5.76 | 5.88 | 5.97 | 6.21 | 6.66 | 7.32 | 7.31 | 7.31 | 7.32 | 7.35 |
| 5 | 6.45 | 6.61 | 6.84 | 7.09 | 7.29 | 7.46 | 7.58 | 7.84 | 8.39 | 9.21 | 9.16 | 9.14 | 9.11 | 9.07 |
| 6 | 7.62 | 7.87 | 8.18 | 8.51 | 8.79 | 9.01 | 9.18 | 9.46 | 10.12 | 11.10 | 11.01 | 10.98 | 10.92 | 10.82 |
| 7 | 8.72 | 9.07 | 9.47 | 9.90 | 10.26 | 10.55 | 10.77 | 11.08 | 11.84 | 12.99 | 12.88 | 12.83 | 12.74 | 12.59 |
| 8 | 9.77 | 10.21 | 10.71 | 11.24 | 11.69 | 12.06 | 12.34 | 12.69 | 13.56 | 14.86 | 14.75 | 14.68 | 14.57 | 14.37 |
| 9 | 10.74 | 11.29 | 11.90 | 12.55 | 13.08 | 13.52 | 13.87 | 14.28 | 15.27 | 16.73 | 16.61 | 16.54 | 16.41 | 16.14 |
| 10 | 11.66 | 12.32 | 13.05 | 13.79 | 14.43 | 14.97 | 15.38 | 15.86 | 16.96 | 18.59 | 18.47 | 18.39 | 18.24 | 17.92 |
Standard ratings (EN 328 / Eurovent)
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.471 |
| SC2 | 0 | 8 | 12.687 |
| SC3 | -18 | 7 | 10.048 |
| SC4 | -25 | 6 | 8.175 |
| SC5 | -34 | 6 | 7.674 |
Dimensions
| A | 1667 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1667 mm |
|---|---|
| Width | 650 mm |
| Height | 606 mm |
Downloads
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.