- Catalogue
- CO₂ DX evaporators
- ED-DC (Double Flow)
- ED-DC-135AC4-A21 C
CO2 evaporator ED-DC-135AC4-A21 C
Defrost: None
Product code: ED-DC-135AC4-A21 C
- Fin spacing
- 4.2 mm
- Fans
- 1 × ⌀350 mm
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
Model nomenclature
How to read the code of this model.
-
A
Model code (series): ED-DC — ED-DC - double-flow CO₂ (R744) DX unit cooler
-
B
Number of fans: 1 — Number of fans (one digit).
-
C
Fan diameter: 35 — Ø350 mm
-
D
Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
-
E
Dimensional data - tube rows: C — 4 tube rows
-
F
Fin spacing: 4 — Fin spacing about 4 mm
-
G
Generation code: A — Generation A
-
H
Fan data: 21 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole
Data
| External surface | 15.7 m² |
|---|---|
| Inner volume | 2.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 41 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø12,7 |
| ED-DC-135AC4-A21 C | None |
|---|
Performance
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R744, dew point -8 °C, air inlet 0 °C (TD 8 K)
- Single phase
- 3.948 kW
Capacity matrix [kW]
R744, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
Single phase
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.69 | 1.69 | 1.71 | 1.74 | 1.77 | 1.79 | 1.82 | 1.87 | 2.00 | 2.19 | 2.19 | 2.19 | 2.20 | 2.21 |
| 5 | 2.14 | 2.14 | 2.17 | 2.22 | 2.26 | 2.29 | 2.32 | 2.38 | 2.54 | 2.78 | 2.77 | 2.76 | 2.76 | 2.76 |
| 6 | 2.60 | 2.60 | 2.64 | 2.70 | 2.75 | 2.80 | 2.83 | 2.89 | 3.09 | 3.38 | 3.35 | 3.35 | 3.34 | 3.32 |
| 7 | 3.04 | 3.06 | 3.11 | 3.19 | 3.25 | 3.31 | 3.35 | 3.42 | 3.65 | 3.99 | 3.95 | 3.94 | 3.92 | 3.89 |
| 8 | 3.47 | 3.51 | 3.58 | 3.67 | 3.75 | 3.82 | 3.87 | 3.95 | 4.21 | 4.60 | 4.56 | 4.54 | 4.51 | 4.46 |
| 9 | 3.89 | 3.95 | 4.04 | 4.15 | 4.25 | 4.33 | 4.39 | 4.48 | 4.78 | 5.22 | 5.17 | 5.14 | 5.10 | 5.04 |
| 10 | 4.31 | 4.38 | 4.49 | 4.63 | 4.74 | 4.84 | 4.91 | 5.01 | 5.34 | 5.84 | 5.78 | 5.75 | 5.70 | 5.63 |
Standard ratings (EN 328 / Eurovent)
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.777 |
| SC2 | 0 | 8 | 3.948 |
| SC3 | -18 | 7 | 3.215 |
| SC4 | -25 | 6 | 2.644 |
| SC5 | -34 | 6 | 2.598 |
Dimensions
| A | 948 mm |
|---|---|
| B | 1030 mm |
| C | 285 mm |
| F | 985 mm |
| G | 367 mm |
| E1 | 635 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø12,7 |
| Length | 948 mm |
|---|---|
| Width | 1030 mm |
| Height | 367 mm |
Downloads
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.