- Catalogue
- CO₂ DX evaporators
- EG-DC (Angled Ceiling Type)
- EG-DC-130BE7-A21 C
CO2 evaporator EG-DC-130BE7-A21 C
Defrost: None
Product code: EG-DC-130BE7-A21 C
- Fin spacing
- 7.0 mm
- Fans
- 1 × ⌀300 mm
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
Model nomenclature
How to read the code of this model.
-
A
Model code (series): EG-DC — EG-DC - angled ceiling CO₂ (R744) DX unit cooler
-
B
Number of fans: 1 — Number of fans (one digit).
-
C
Fan diameter: 30 — Ø300 mm
-
D
Dimensional data - coil size letter: B — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
-
E
Dimensional data - tube rows: E — 6 tube rows
-
F
Fin spacing: 7 — Fin spacing about 7 mm
-
G
Generation code: A — Generation A
-
H
Fan data: 21 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole
Data
| External surface | 7.4 m² |
|---|---|
| Inner volume | 1.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 22 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 65.3 dB(A) |
| Energy class | B |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø9,52 |
| EG-DC-130BE7-A21 C | None |
|---|
Performance
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R744, dew point -8 °C, air inlet 0 °C (TD 8 K)
- Single phase
- 1.937 kW
Capacity matrix [kW]
R744, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
Single phase
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.83 | 0.84 | 0.85 | 0.87 | 0.89 | 0.90 | 0.91 | 0.94 | 1.01 | 1.10 | 1.10 | 1.10 | 1.09 | 1.10 |
| 5 | 1.04 | 1.05 | 1.07 | 1.10 | 1.12 | 1.14 | 1.15 | 1.19 | 1.27 | 1.39 | 1.37 | 1.37 | 1.36 | 1.35 |
| 6 | 1.25 | 1.27 | 1.29 | 1.33 | 1.36 | 1.38 | 1.40 | 1.44 | 1.53 | 1.68 | 1.66 | 1.65 | 1.63 | 1.61 |
| 7 | 1.45 | 1.48 | 1.52 | 1.56 | 1.60 | 1.63 | 1.65 | 1.69 | 1.80 | 1.96 | 1.94 | 1.93 | 1.91 | 1.88 |
| 8 | 1.65 | 1.68 | 1.73 | 1.79 | 1.83 | 1.87 | 1.90 | 1.94 | 2.07 | 2.26 | 2.23 | 2.21 | 2.19 | 2.15 |
| 9 | 1.83 | 1.88 | 1.94 | 2.01 | 2.06 | 2.11 | 2.14 | 2.19 | 2.33 | 2.55 | 2.51 | 2.50 | 2.47 | 2.42 |
| 10 | 2.01 | 2.07 | 2.15 | 2.23 | 2.29 | 2.35 | 2.38 | 2.44 | 2.60 | 2.84 | 2.80 | 2.78 | 2.75 | 2.69 |
Standard ratings (EN 328 / Eurovent)
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 2.801 |
| SC2 | 0 | 8 | 1.937 |
| SC3 | -18 | 7 | 1.577 |
| SC4 | -25 | 6 | 1.294 |
| SC5 | -34 | 6 | 1.256 |
Dimensions
| A | 826 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E | 515 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø9,52 |
| Length | 826 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Downloads
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.