- Catalogue
- CO₂ DX evaporators
- EG-DC (Angled Ceiling Type)
- EG-DC-230AE4-A21 C
CO2 evaporator EG-DC-230AE4-A21 C
Defrost: None
Product code: EG-DC-230AE4-A21 C
- Fin spacing
- 4.2 mm
- Fans
- 2 × ⌀300 mm
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
Model nomenclature
How to read the code of this model.
-
A
Model code (series): EG-DC — EG-DC - angled ceiling CO₂ (R744) DX unit cooler
-
B
Number of fans: 2 — Number of fans (one digit).
-
C
Fan diameter: 30 — Ø300 mm
-
D
Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
-
E
Dimensional data - tube rows: E — 6 tube rows
-
F
Fin spacing: 4 — Fin spacing about 4 mm
-
G
Generation code: A — Generation A
-
H
Fan data: 21 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole
Data
| External surface | 23.6 m² |
|---|---|
| Inner volume | 3.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 39 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.2 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø9,52 |
| EG-DC-230AE4-A21 C | None |
|---|
Performance
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R744, dew point -8 °C, air inlet 0 °C (TD 8 K)
- Single phase
- 4.537 kW
Capacity matrix [kW]
R744, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
Single phase
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.00 | 2.00 | 2.03 | 2.08 | 2.11 | 2.13 | 2.15 | 2.23 | 2.39 | 2.62 | 2.60 | 2.59 | 2.58 | 2.57 |
| 5 | 2.50 | 2.52 | 2.56 | 2.62 | 2.67 | 2.70 | 2.72 | 2.80 | 2.99 | 3.27 | 3.22 | 3.20 | 3.18 | 3.13 |
| 6 | 2.99 | 3.02 | 3.09 | 3.17 | 3.23 | 3.28 | 3.30 | 3.38 | 3.60 | 3.93 | 3.86 | 3.83 | 3.79 | 3.71 |
| 7 | 3.46 | 3.52 | 3.61 | 3.71 | 3.79 | 3.84 | 3.87 | 3.96 | 4.21 | 4.59 | 4.51 | 4.47 | 4.41 | 4.30 |
| 8 | 3.91 | 4.00 | 4.11 | 4.24 | 4.34 | 4.41 | 4.45 | 4.54 | 4.83 | 5.26 | 5.16 | 5.11 | 5.03 | 4.90 |
| 9 | 4.35 | 4.47 | 4.61 | 4.77 | 4.89 | 4.97 | 5.02 | 5.12 | 5.45 | 5.93 | 5.82 | 5.76 | 5.67 | 5.50 |
| 10 | 4.77 | 4.92 | 5.09 | 5.28 | 5.43 | 5.53 | 5.59 | 5.70 | 6.07 | 6.60 | 6.48 | 6.41 | 6.31 | 6.12 |
Standard ratings (EN 328 / Eurovent)
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.475 |
| SC2 | 0 | 8 | 4.537 |
| SC3 | -18 | 7 | 3.745 |
| SC4 | -25 | 6 | 3.090 |
| SC5 | -34 | 6 | 2.995 |
Dimensions
| A | 1946 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø9,52 |
| Length | 1946 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Downloads
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.