- Catalogue
- CO₂ DX evaporators
- EG-DC (Angled Ceiling Type)
- EG-DC-425AB7-A23 C
CO2 evaporator EG-DC-425AB7-A23 C
Defrost: None
Product code: EG-DC-425AB7-A23 C
- Fin spacing
- 7.0 mm
- Fans
- 4 × ⌀250 mm
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
Model nomenclature
How to read the code of this model.
-
A
Model code (series): EG-DC — EG-DC - angled ceiling CO₂ (R744) DX unit cooler
-
B
Number of fans: 4 — Number of fans (one digit).
-
C
Fan diameter: 25 — Ø250 mm
-
D
Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
-
E
Dimensional data - tube rows: B — 3 tube rows
-
F
Fin spacing: 7 — Fin spacing about 7 mm
-
G
Generation code: A — Generation A
-
H
Fan data: 23 — Ø250: 230V/1Ph/50Hz, 4-pole
Data
| External surface | 11.2 m² |
|---|---|
| Inner volume | 2.8 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 42 kg |
| Quantity | 4 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 260 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.4 dB(A) |
| Energy class | E |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø15,9 |
| EG-DC-425AB7-A23 C | None |
|---|
Performance
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R744, dew point -8 °C, air inlet 0 °C (TD 8 K)
- Single phase
- 3.198 kW
Capacity matrix [kW]
R744, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
Single phase
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.29 | 1.32 | 1.37 | 1.42 | 1.46 | 1.50 | 1.53 | 1.59 | 1.71 | 1.88 | 1.88 | 1.88 | 1.88 | 1.89 |
| 5 | 1.58 | 1.63 | 1.70 | 1.77 | 1.84 | 1.89 | 1.93 | 2.00 | 2.14 | 2.35 | 2.35 | 2.34 | 2.34 | 2.34 |
| 6 | 1.85 | 1.93 | 2.02 | 2.12 | 2.20 | 2.27 | 2.33 | 2.40 | 2.57 | 2.83 | 2.82 | 2.81 | 2.80 | 2.78 |
| 7 | 2.11 | 2.21 | 2.33 | 2.45 | 2.55 | 2.64 | 2.72 | 2.80 | 3.00 | 3.30 | 3.28 | 3.28 | 3.26 | 3.24 |
| 8 | 2.35 | 2.48 | 2.62 | 2.77 | 2.90 | 3.01 | 3.10 | 3.20 | 3.42 | 3.76 | 3.75 | 3.74 | 3.72 | 3.69 |
| 9 | 2.57 | 2.73 | 2.90 | 3.08 | 3.23 | 3.36 | 3.47 | 3.59 | 3.84 | 4.22 | 4.21 | 4.20 | 4.18 | 4.15 |
| 10 | ≈ 2.78 | 2.96 | 3.16 | 3.37 | 3.55 | 3.71 | 3.84 | 3.98 | 4.26 | 4.68 | 4.68 | 4.66 | 4.65 | 4.60 |
Standard ratings (EN 328 / Eurovent)
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.676 |
| SC2 | 0 | 8 | 3.198 |
| SC3 | -18 | 7 | 2.493 |
| SC4 | -25 | 6 | 2.020 |
| SC5 | -34 | 6 | 1.871 |
Dimensions
| A | 1786 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 378 mm |
| E2 | 360 mm |
| E | 1475 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø15,9 |
| Length | 1786 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Downloads
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.