EA-DA-163BE7-C27 C
14.33 kW
Defrost: None
Product code: EA-DA-435BE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,158 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 50.6 m² |
| Inner volume | 18.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 131 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-DA-435BE7-C21 C | None |
|---|---|
| EA-DA-435BE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.00 | 5.31 | 5.58 | 5.80 | 5.92 | 5.97 | 5.95 | 6.12 | 6.53 | 7.09 | 6.93 | 6.88 | 6.81 | 6.71 |
| 5 | 6.24 | 6.75 | 7.20 | 7.58 | 7.80 | 7.94 | 7.97 | 8.15 | 8.67 | 9.42 | 9.16 | 9.07 | 8.92 | 8.69 |
| 6 | ≈ 7.28 | 8.00 | 8.66 | 9.22 | 9.63 | 9.82 | 9.95 | 10.18 | 10.84 | 11.78 | 11.48 | 11.35 | 11.16 | 10.81 |
| 7 | ≈ 8.19 | 9.08 | 9.92 | 10.56 | 11.12 | 11.50 | 11.72 | 11.99 | 12.78 | 13.93 | 13.63 | 13.49 | 13.27 | 12.87 |
| 8 | ≈ 6.10 | ≈ 10.03 | 10.95 | 11.89 | 12.62 | 13.13 | 13.46 | 13.80 | 14.71 | 16.03 | 15.72 | 15.55 | 15.29 | 14.81 |
| 9 | ≈ 2.96 | ≈ 9.87 | ≈ 11.99 | 13.14 | 14.04 | 14.72 | 15.15 | 15.58 | 16.62 | 18.13 | 17.81 | 17.62 | 17.32 | 16.77 |
| 10 | ≈ 3.22 | ≈ 7.39 | ≈ 12.94 | 14.29 | 15.40 | 16.24 | 16.81 | 17.34 | 18.52 | 20.22 | 19.90 | 19.70 | 19.37 | 18.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 19.895 |
| SC2 | 0 | 8 | 13.798 |
| SC3 | -18 | 7 | 10.807 |
| SC4 | -25 | 6 | 8.659 |
| SC5 | -34 | 6 | 7.438 |
| A | 2457 mm |
|---|---|
| B | 730 mm |
| C | 530 mm |
| F | 560 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2457 mm |
|---|---|
| Width | 730 mm |
| Height | 530 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.