EA-DA-450BE7-C22 C
53.80 kW
Defrost: None
Product code: EA-DA-450BE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 28,879 m³/h |
|---|---|
| Air throw | 25 m |
| External surface | 236.6 m² |
| Inner volume | 70.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 329 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 2,720 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 84.9 dB(A) |
| Energy class | C |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-DA-450BE7-C21 C | None |
|---|---|
| EA-DA-450BE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 21.24 | 20.96 | 20.86 | 20.88 | 20.83 | 20.74 | 20.63 | 20.89 | 22.20 | 24.07 | 23.57 | 23.38 | 23.12 | 22.72 |
| 5 | 27.85 | 27.64 | 27.67 | 27.80 | 27.78 | 27.66 | 27.48 | 27.69 | 29.38 | 31.80 | 31.03 | 30.76 | 30.38 | 29.81 |
| 6 | 34.34 | 34.50 | 34.77 | 35.08 | 35.16 | 35.05 | 34.83 | 35.00 | 37.09 | 40.11 | 39.03 | 38.63 | 38.06 | 37.18 |
| 7 | 40.60 | 41.22 | 41.86 | 42.48 | 42.75 | 42.76 | 42.51 | 42.65 | 45.17 | 48.84 | 47.47 | 46.94 | 46.16 | 44.93 |
| 8 | 46.56 | 47.56 | 48.69 | 49.71 | 50.28 | 50.49 | 50.40 | 50.58 | 53.57 | 57.95 | 56.30 | 55.65 | 54.68 | 53.12 |
| 9 | 51.74 | 53.45 | 55.10 | 56.63 | 57.64 | 58.23 | 58.37 | 58.65 | 62.14 | 67.23 | 65.40 | 64.63 | 63.50 | 61.62 |
| 10 | 56.62 | 58.96 | 61.15 | 63.14 | 64.44 | 65.26 | 65.66 | 66.23 | 70.28 | 76.21 | 74.48 | 73.73 | 72.48 | 70.26 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 74.477 |
| SC2 | 0 | 8 | 50.580 |
| SC3 | -18 | 7 | 42.622 |
| SC4 | -25 | 6 | 34.769 |
| SC5 | -34 | 6 | 34.418 |
| A | 4487 mm |
|---|---|
| B | 950 mm |
| C | 810 mm |
| F | 710 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 4035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 4487 mm |
|---|---|
| Width | 950 mm |
| Height | 810 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.