Skip to Content

Unit cooler EA-DA-735BE7-C21 C

Unit cooler EA-DA-735BE7-C21 C
Illustrative photo

Producer: Karyer · Line: EA-DA (Fruit and Vegetable)

Product code: EA-DA-735BE7-C21 C

Cooling capacity i
25.10 kW
Air flow
14,272 m³/h
Fin spacing
7.0 mm
Air throw
15 m
Fans
7 × ⌀350 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA-DA — EA-DA - fruit and vegetable unit cooler (blowing fans)
  • C
    Number of fans: 7 — Number of fans (one digit).
  • D
    Fan diameter: 35 — Ø350 mm
  • E
    Dimensional data - coil size letter: B — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • F
    Dimensional data - tube rows: E — 6 tube rows
  • G
    Fin spacing: 7 — Fin spacing about 7 mm
  • H
    Generation code: C — Generation C
  • I
    Fan data: 21 — Ø350: 230V/1Ph/50Hz, 4-pole; Ø500: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 14,272 m³/h
Air throw 15 m
External surface 88.6 m²
Inner volume 33.2 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 214 kg
Fans
Quantity 7
Diameter 350 mm
Speed 1,340 rpm
Power 1,155 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 56.0 dB(A)
Sound power 78.5 dB(A)
Energy class C
Connections
Inlet Ø28
Outlet Ø35
Defrost
EA-DA-735BE7-C21 C None
EA-DA-735BE7-C21 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
24.267 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 8.29 9.04 9.74 10.34 10.74 10.97 11.05 11.42 12.21 13.30 13.04 12.95 12.83 12.65
5 ≈ 10.14 11.26 12.32 13.26 13.93 14.38 14.51 14.95 15.92 17.38 17.02 16.87 16.64 16.25
6 ≈ 9.22 ≈ 13.08 14.46 15.51 16.47 17.15 17.58 18.10 19.33 21.13 20.76 20.59 20.32 19.79
7 not rated ≈ 12.34 ≈ 16.15 17.72 18.99 19.93 20.56 21.21 22.66 24.80 24.39 24.19 23.84 23.18
8 ≈ 4.79 ≈ 8.88 ≈ 17.83 19.76 21.36 22.58 23.44 24.27 25.95 28.41 28.02 27.78 27.38 26.61
9 5.27 ≈ 5.21 ≈ 19.36 21.64 23.57 25.12 26.23 27.26 29.18 31.99 31.63 31.38 30.93 30.06
10 5.74 ≈ 5.67 ≈ 11.72 ≈ 23.34 25.65 27.53 28.92 30.18 32.35 35.52 35.22 34.96 34.49 33.53

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 35.216
SC2 0 8 24.267
SC3 -18 7 18.262
SC4 -25 6 14.459
SC5 -34 6 10.988

Dimensions

Dimension drawing of EA-DA-735BE7-C21 C
Dimension drawing
Dimensions as drawn
A 3957 mm
B 730 mm
C 530 mm
F 560 mm
E1 518 mm
E2 500 mm
E 3535 mm
D IN 1 x Ø28
D OUT 1 x Ø35
Overall [mm]
Length 3957 mm
Width 730 mm
Height 530 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.