Skip to Content

Unit cooler EA-DA-x-435BE7-B21 C

Unit cooler EA-DA-x-435BE7-B21 C
Illustrative photo

Producer: Karyer · Line: EA-DA (Fruit and Vegetable)

Product code: EA-DA-x-435BE7-B21 C

Cooling capacity i
12.20 kW
Air flow
8,161 m³/h
Fin spacing
7.0 mm
Air throw
14 m
Fans
4 × ⌀350 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA-DA — EA-DA - fruit and vegetable unit cooler (blowing fans)
  • C
    Number of fans: 4 — Number of fans (one digit).
  • D
    Fan diameter: 35 — Ø350 mm
  • E
    Dimensional data - coil size letter: B — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • F
    Dimensional data - tube rows: E — 6 tube rows
  • G
    Fin spacing: 7 — Fin spacing about 7 mm
  • H
    Generation code: B — Generation B
  • I
    Fan data: 21 — Ø350: 230V/1Ph/50Hz, 4-pole; Ø500: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 8,161 m³/h
Air throw 14 m
External surface 50.6 m²
Inner volume 18.8 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 129 kg
Fans
Quantity 4
Diameter 350 mm
Speed 1,340 rpm
Power 660 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 54.0 dB(A)
Sound power 76.0 dB(A)
Energy class D
Connections
Inlet Ø19
Outlet Ø22
Defrost
EA-DA-x-435BE7-B21 C None
EA-DA-x-435BE7-B21 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
11.808 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 not rated 4.19 4.59 4.95 5.21 5.38 5.45 5.67 6.07 6.62 6.51 6.45 6.39 6.32
5 not rated 5.18 5.76 6.29 6.60 6.89 7.07 7.32 7.83 8.58 8.46 8.40 8.32 8.17
6 not rated not rated 6.40 7.28 7.83 8.25 8.53 8.85 9.47 10.38 10.25 10.18 10.07 9.86
7 ≈ 2.23 ≈ 3.11 ≈ 6.76 ≈ 8.26 8.98 9.55 9.95 10.35 11.08 12.18 12.04 11.97 11.82 11.55
8 2.50 ≈ 2.46 ≈ 5.31 ≈ 9.16 10.05 10.77 11.32 11.81 12.67 13.93 13.83 13.74 13.58 13.26
9 2.76 ≈ 2.72 ≈ 6.36 ≈ 9.97 11.03 11.92 12.61 13.23 14.21 15.65 15.59 15.50 15.34 14.98
10 3.01 2.97 ≈ 2.98 ≈ 9.40 ≈ 11.95 13.01 13.85 14.60 15.71 17.34 17.32 17.25 17.08 16.70

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 17.323
SC2 0 8 11.808
SC3 -18 7 8.566
SC4 -25 6 6.403
SC5 -34 6 —

Dimensions

Dimension drawing of EA-DA-x-435BE7-B21 C
Dimension drawing
Dimensions as drawn
A 2457 mm
B 730 mm
C 530 mm
F 560 mm
E1 518 mm
E2 500 mm
E 2035 mm
D IN 1 x Ø19
D OUT 1 x Ø22
Overall [mm]
Length 2457 mm
Width 730 mm
Height 530 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.