Producer: Karyer · Line: EA-DA (Fruit and Vegetable)

Product code: EA-DA-x-450BE7-B21 C

Cooling capacity i
34.90 kW
Air flow
28,914 m³/h
Fin spacing
7.0 mm
Air throw
25 m
Fans
4 × ⌀500 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA-DA — EA-DA - fruit and vegetable unit cooler (blowing fans)
  • C
    Number of fans: 4 — Number of fans (one digit).
  • D
    Fan diameter: 50 — Ø500 mm
  • E
    Dimensional data - coil size letter: B — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • F
    Dimensional data - tube rows: E — 6 tube rows
  • G
    Fin spacing: 7 — Fin spacing about 7 mm
  • H
    Generation code: B — Generation B
  • I
    Fan data: 21 — Ø350: 230V/1Ph/50Hz, 4-pole; Ø500: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 28,914 m³/h
Air throw 25 m
External surface 236.6 m²
Inner volume 68.1 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 315 kg
Fans
Quantity 4
Diameter 500 mm
Speed 1,300 rpm
Power 2,720 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 62.0 dB(A)
Sound power 84.9 dB(A)
Energy class D
Connections
Inlet Ø22
Outlet Ø42
Defrost
EA-DA-x-450BE7-B21 C None
EA-DA-x-450BE7-B21 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
33.775 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 not rated not rated 13.04 14.04 14.60 15.12 15.45 15.92 17.01 18.57 18.32 18.19 18.01 17.72
5 not rated not rated 15.94 17.46 18.65 19.56 20.23 20.90 22.38 24.53 24.35 24.26 24.11 23.83
6 ≈ 5.77 ≈ 12.86 18.53 20.47 22.10 23.40 24.38 25.29 27.10 29.76 29.60 29.51 29.34 28.99
7 6.60 not rated ≈ 20.78 23.22 25.33 27.06 28.40 29.59 31.76 34.96 34.86 34.77 34.59 34.20
8 7.41 ≈ 7.28 ≈ 14.25 ≈ 25.73 28.33 30.52 32.27 33.78 36.31 40.07 40.09 40.02 39.85 39.43
9 8.20 8.07 ≈ 8.11 ≈ 28.00 31.10 33.78 35.97 37.83 40.75 45.07 45.24 45.21 45.08 44.67
10 8.97 8.84 ≈ 8.84 ≈ 25.13 ≈ 33.66 36.83 39.49 41.75 45.04 49.94 50.32 50.33 50.26 49.87

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 50.315
SC2 0 8 33.775
SC3 -18 7 24.107
SC4 -25 6 18.527
SC5 -34 6 —

Dimensions

Dimension drawing of EA-DA-x-450BE7-B21 C
Dimension drawing
Dimensions as drawn
A 4487 mm
B 950 mm
C 810 mm
F 710 mm
E1 1018 mm
E2 1000 mm
E 4035 mm
D IN 1 x Ø22
D OUT 1 x Ø42
Overall [mm]
Length 4487 mm
Width 950 mm
Height 810 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.