EA-DI-263GC7-A13 C
37.19 kW
Defrost: None
Product code: EA-DI-163GI7-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,666 m³/h |
|---|---|
| External surface | 182.8 m² |
| Inner volume | 54.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 290 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-DI-163GI7-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.90 | 14.85 | 14.88 | 14.96 | 14.96 | 14.92 | 14.84 | 15.02 | 15.96 | 17.30 | 16.95 | 16.82 | 16.65 | 16.35 |
| 5 | 19.32 | 19.45 | 19.58 | 19.79 | 19.85 | 19.82 | 19.70 | 19.86 | 21.07 | 22.81 | 22.24 | 22.04 | 21.75 | 21.32 |
| 6 | 23.52 | 23.97 | 24.40 | 24.80 | 24.98 | 24.97 | 24.87 | 25.01 | 26.50 | 28.67 | 27.89 | 27.59 | 27.16 | 26.49 |
| 7 | 27.49 | 28.34 | 29.12 | 29.69 | 30.08 | 30.22 | 30.18 | 30.33 | 32.13 | 34.75 | 33.78 | 33.40 | 32.83 | 31.91 |
| 8 | 31.19 | 32.35 | 33.53 | 34.57 | 35.21 | 35.53 | 35.58 | 35.78 | 37.92 | 41.04 | 39.92 | 39.45 | 38.76 | 37.59 |
| 9 | 34.33 | 36.04 | 37.62 | 39.04 | 39.99 | 40.57 | 40.87 | 41.26 | 43.78 | 47.40 | 46.16 | 45.63 | 44.82 | 43.42 |
| 10 | 37.29 | 39.50 | 41.53 | 43.32 | 44.55 | 45.35 | 45.78 | 46.25 | 49.10 | 53.27 | 52.09 | 51.56 | 50.74 | 49.30 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.45 | 12.35 | 12.35 | 12.40 | 12.41 | 12.38 | 12.31 | 12.56 | 13.37 | 14.52 | 14.25 | 14.16 | 14.04 | 13.87 |
| 5 | 16.03 | 16.02 | 16.10 | 16.23 | 16.25 | 16.21 | 16.10 | 16.30 | 17.31 | 18.77 | 18.31 | 18.15 | 17.92 | 17.58 |
| 6 | 19.63 | 19.77 | 19.94 | 20.17 | 20.26 | 20.23 | 20.09 | 20.25 | 21.47 | 23.25 | 22.60 | 22.35 | 22.00 | 21.43 |
| 7 | 23.04 | 23.42 | 23.82 | 24.20 | 24.38 | 24.37 | 24.23 | 24.36 | 25.81 | 27.92 | 27.08 | 26.75 | 26.26 | 25.46 |
| 8 | 26.28 | 26.97 | 27.62 | 28.21 | 28.52 | 28.60 | 28.47 | 28.56 | 30.23 | 32.68 | 31.70 | 31.29 | 30.67 | 29.65 |
| 9 | 29.33 | 30.38 | 31.21 | 32.05 | 32.55 | 32.74 | 32.69 | 32.84 | 34.77 | 37.57 | 36.46 | 35.96 | 35.23 | 34.05 |
| 10 | 32.18 | 33.46 | 34.74 | 35.89 | 36.59 | 36.93 | 36.96 | 37.16 | 39.35 | 42.51 | 41.28 | 40.73 | 39.88 | 38.55 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 52.085 | 41.284 |
| SC2 | 0 | 8 | 35.781 | 28.564 |
| SC3 | -18 | 7 | 29.875 | 24.296 |
| SC4 | -25 | 6 | 24.395 | 19.935 |
| SC5 | -34 | 6 | 23.644 | 19.681 |
| A | 1725 mm |
|---|---|
| B | 1200 mm |
| C | 1150 mm |
| F | 1160 mm |
| G | 1740 mm |
| E | 1335 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1740 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.