EA-DI-163GI4-A13 C
42.65 kW
Defrost: None
Product code: EA-DI-191GG7-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 22,959 m³/h |
|---|---|
| External surface | 175.8 m² |
| Inner volume | 53.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 341 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 91.5 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-DI-191GG7-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 16.69 | 16.52 | 16.45 | 16.46 | 16.39 | 16.28 | 16.13 | 16.55 | 17.59 | 19.05 | 18.64 | 18.50 | 18.29 | 17.98 |
| 5 | 21.99 | 21.98 | 21.99 | 22.10 | 22.05 | 21.89 | 21.65 | 22.00 | 23.38 | 25.31 | 24.70 | 24.49 | 24.21 | 23.81 |
| 6 | 27.14 | 27.46 | 27.77 | 28.06 | 28.10 | 27.93 | 27.63 | 27.92 | 29.61 | 32.00 | 31.07 | 30.73 | 30.25 | 29.54 |
| 7 | 32.07 | 32.83 | 33.52 | 33.99 | 34.23 | 34.19 | 33.90 | 34.14 | 36.16 | 39.06 | 37.82 | 37.35 | 36.65 | 35.56 |
| 8 | 36.70 | 37.81 | 38.97 | 39.95 | 40.46 | 40.57 | 40.35 | 40.59 | 42.98 | 46.47 | 44.95 | 44.35 | 43.46 | 42.01 |
| 9 | 40.55 | 42.28 | 43.87 | 45.28 | 46.16 | 46.62 | 46.68 | 47.14 | 49.97 | 54.02 | 52.31 | 51.60 | 50.53 | 48.72 |
| 10 | 44.24 | 46.54 | 48.63 | 50.46 | 51.60 | 52.25 | 52.45 | 52.98 | 56.19 | 60.87 | 59.28 | 58.57 | 57.50 | 55.57 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 13.65 | 14.60 | 15.89 | 15.65 | 15.57 | 15.42 | 15.21 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 19.66 | 19.36 |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 59.276 | — |
| SC2 | 0 | 8 | 40.591 | — |
| SC3 | -18 | 7 | 34.127 | — |
| SC4 | -25 | 6 | 27.772 | — |
| SC5 | -34 | 6 | 27.250 | — |
| A | 1725 mm |
|---|---|
| B | 1100 mm |
| C | 1350 mm |
| F | 1060 mm |
| G | 1900 mm |
| E | 1335 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1900 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.