EA-DI-263GG7-A13 C
63.24 kW
Defrost: None
Product code: EA-DI-291GE10-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 52,727 m³/h |
|---|---|
| External surface | 190.4 m² |
| Inner volume | 80.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 564 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 93.3 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-DI-291GE10-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 24.03 | 23.52 | 23.20 | 22.99 | 22.72 | 22.42 | 22.09 | 22.28 | 23.54 | 25.37 | 24.67 | 24.42 | 24.06 | 23.54 |
| 5 | 32.40 | 32.00 | 31.84 | 31.74 | 31.46 | 31.06 | 30.57 | 30.80 | 32.61 | 35.15 | 34.13 | 33.76 | 33.20 | 32.36 |
| 6 | 40.61 | 40.75 | 40.93 | 41.10 | 40.94 | 40.51 | 39.94 | 40.12 | 42.46 | 45.75 | 44.26 | 43.74 | 43.00 | 41.89 |
| 7 | 48.49 | 49.29 | 50.01 | 50.63 | 50.63 | 50.40 | 49.86 | 50.01 | 52.88 | 57.00 | 55.08 | 54.37 | 53.34 | 51.74 |
| 8 | 55.88 | 57.19 | 58.66 | 59.90 | 60.46 | 60.50 | 60.11 | 60.29 | 63.79 | 68.82 | 66.54 | 65.66 | 64.35 | 62.26 |
| 9 | 62.00 | 64.24 | 66.32 | 68.20 | 69.37 | 69.98 | 70.13 | 70.71 | 74.94 | 80.99 | 78.43 | 77.39 | 75.86 | 73.35 |
| 10 | 67.92 | 70.98 | 73.78 | 76.27 | 77.87 | 78.78 | 79.12 | 79.79 | 84.64 | 91.75 | 89.45 | 88.47 | 87.02 | 84.60 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 20.50 | 20.02 | 19.75 | 19.61 | 19.43 | 19.22 | 19.00 | 19.35 | 20.47 | 22.12 | 21.59 | 21.40 | 21.13 | 20.73 |
| 5 | 27.38 | 26.98 | 26.77 | 26.67 | 26.45 | 26.15 | 25.78 | 26.08 | 27.67 | 29.90 | 29.11 | 28.84 | 28.47 | 27.94 |
| 6 | 34.43 | 34.24 | 34.14 | 34.19 | 34.02 | 33.68 | 33.21 | 33.43 | 35.41 | 38.20 | 37.02 | 36.60 | 36.02 | 35.16 |
| 7 | 41.25 | 41.45 | 41.72 | 42.01 | 41.96 | 41.63 | 41.11 | 41.26 | 43.65 | 47.08 | 45.50 | 44.92 | 44.08 | 42.76 |
| 8 | 47.81 | 48.52 | 49.22 | 49.86 | 50.04 | 49.86 | 49.29 | 49.41 | 52.24 | 56.36 | 54.39 | 53.61 | 52.45 | 50.60 |
| 9 | 54.03 | 55.18 | 56.42 | 57.51 | 58.02 | 58.06 | 57.66 | 57.79 | 61.12 | 65.97 | 63.63 | 62.67 | 61.24 | 58.90 |
| 10 | 59.41 | 61.30 | 63.11 | 64.76 | 65.74 | 66.26 | 66.07 | 66.31 | 70.15 | 75.70 | 73.12 | 72.00 | 70.29 | 67.57 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 89.445 | 73.118 |
| SC2 | 0 | 8 | 60.287 | 49.409 |
| SC3 | -18 | 7 | 50.596 | 42.022 |
| SC4 | -25 | 6 | 40.930 | 34.144 |
| SC5 | -34 | 6 | 40.697 | 34.431 |
| A | 3025 mm |
|---|---|
| B | 1000 mm |
| C | 1350 mm |
| F | 960 mm |
| G | 1800 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 3025 mm |
|---|---|
| Width | 1800 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.