EA-DI-280GG4-A01 C
83.77 kW
Defrost: None
Product code: EA-DI-291GE4-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 46,792 m³/h |
|---|---|
| External surface | 390.9 m² |
| Inner volume | 80.3 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 592 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 94.3 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-DI-291GE4-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 32.85 | 32.84 | 32.88 | 33.07 | 33.05 | 32.91 | 32.67 | 33.56 | 35.68 | 38.66 | 37.88 | 37.59 | 37.18 | 36.58 |
| 5 | 42.77 | 43.40 | 43.98 | 44.48 | 44.59 | 44.40 | 43.97 | 44.75 | 47.59 | 51.57 | 50.33 | 49.93 | 49.39 | 48.61 |
| 6 | 52.30 | 53.59 | 54.96 | 56.09 | 56.60 | 56.60 | 56.19 | 56.89 | 60.37 | 65.32 | 63.48 | 62.81 | 61.87 | 60.46 |
| 7 | 60.31 | 62.72 | 64.93 | 66.89 | 68.09 | 68.70 | 68.81 | 69.74 | 73.96 | 80.04 | 77.66 | 76.75 | 75.42 | 73.31 |
| 8 | 67.68 | 71.13 | 74.25 | 76.96 | 78.69 | 79.63 | 79.91 | 80.89 | 85.89 | 93.22 | 90.88 | 89.96 | 88.56 | 86.29 |
| 9 | 74.50 | 79.09 | 83.25 | 86.83 | 89.22 | 90.58 | 91.11 | 92.19 | 97.87 | 106.21 | 103.53 | 102.41 | 100.72 | 97.92 |
| 10 | 80.74 | 86.57 | 91.86 | 96.46 | 99.61 | 101.44 | 102.29 | 103.60 | 109.98 | 119.32 | 116.37 | 115.07 | 113.11 | 109.78 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 27.80 | 29.72 | 32.35 | 31.93 | 31.71 | 31.44 | 31.02 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 36.19 | 38.55 | 41.86 | 40.89 | 40.59 | 40.18 | 39.62 |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 116.373 | — |
| SC2 | 0 | 8 | 80.890 | — |
| SC3 | -18 | 7 | 67.446 | — |
| SC4 | -25 | 6 | 54.960 | — |
| SC5 | -34 | 6 | 52.713 | — |
| A | 3025 mm |
|---|---|
| B | 1000 mm |
| C | 1350 mm |
| F | 960 mm |
| G | 1800 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 3025 mm |
|---|---|
| Width | 1800 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.