EA-DI-363GE7-A13 C
81.03 kW
Defrost: None
Product code: EA-DI-291GG7-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 45,934 m³/h |
|---|---|
| External surface | 351.5 m² |
| Inner volume | 105.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 627 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 94.5 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-DI-291GG7-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 30.69 | 30.93 | 31.20 | 31.46 | 31.48 | 31.33 | 31.06 | 31.87 | 33.91 | 36.69 | 35.87 | 35.56 | 35.12 | 34.46 |
| 5 | 39.81 | 40.72 | 41.52 | 42.20 | 42.44 | 42.30 | 41.95 | 42.70 | 45.39 | 49.17 | 47.94 | 47.53 | 46.96 | 46.10 |
| 6 | 48.23 | 50.11 | 51.47 | 52.83 | 53.54 | 53.73 | 53.47 | 54.19 | 57.52 | 62.27 | 60.48 | 59.83 | 58.89 | 57.43 |
| 7 | 55.64 | 58.40 | 60.91 | 63.13 | 64.57 | 65.37 | 65.35 | 66.14 | 70.18 | 76.03 | 73.84 | 72.98 | 71.69 | 69.61 |
| 8 | 62.16 | 65.93 | 69.38 | 72.38 | 74.41 | 75.61 | 76.11 | 77.20 | 82.02 | 89.11 | 86.95 | 86.07 | 84.73 | 82.34 |
| 9 | 68.12 | 72.99 | 77.46 | 81.38 | 84.10 | 85.79 | 86.57 | 87.85 | 93.34 | 101.39 | 98.98 | 97.94 | 96.35 | 93.57 |
| 10 | ≈ 73.53 | 79.58 | 85.17 | 90.09 | 93.53 | 95.80 | 96.98 | 98.53 | 104.71 | 113.74 | 111.14 | 109.95 | 108.11 | 104.84 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 26.12 | 27.94 | 30.38 | 29.88 | 29.70 | 29.40 | 28.94 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 37.18 |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 111.139 | — |
| SC2 | 0 | 8 | 77.198 | — |
| SC3 | -18 | 7 | 63.793 | — |
| SC4 | -25 | 6 | 51.465 | — |
| SC5 | -34 | 6 | 48.704 | — |
| A | 3025 mm |
|---|---|
| B | 1100 mm |
| C | 1350 mm |
| F | 1060 mm |
| G | 1900 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 3025 mm |
|---|---|
| Width | 1900 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.