EA-DI-363GG7-A08 C
86.40 kW
Defrost: None
Product code: EA-DI-291GI10-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 45,144 m³/h |
|---|---|
| External surface | 317.4 m² |
| Inner volume | 131.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 699 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 94.7 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø80 |
| EA-DI-291GI10-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 33.49 | 33.43 | 33.48 | 33.57 | 33.44 | 33.15 | 32.73 | 33.50 | 35.67 | 38.61 | 37.66 | 37.30 | 36.79 | 36.03 |
| 5 | 43.70 | 44.19 | 44.69 | 45.04 | 45.09 | 44.82 | 44.29 | 44.95 | 47.73 | 51.63 | 50.16 | 49.66 | 48.98 | 48.01 |
| 6 | 53.29 | 54.64 | 55.85 | 56.86 | 57.25 | 57.13 | 56.55 | 57.11 | 60.53 | 65.42 | 63.28 | 62.51 | 61.40 | 59.66 |
| 7 | 62.24 | 64.65 | 66.44 | 68.23 | 69.19 | 69.43 | 69.07 | 69.62 | 73.75 | 79.74 | 77.10 | 76.08 | 74.56 | 72.03 |
| 8 | 69.93 | 73.44 | 76.51 | 79.21 | 80.94 | 81.86 | 81.76 | 82.42 | 87.32 | 94.48 | 91.48 | 90.24 | 88.32 | 85.10 |
| 9 | 77.18 | 81.64 | 85.71 | 89.26 | 91.63 | 92.91 | 93.38 | 94.47 | 100.24 | 108.67 | 105.83 | 104.54 | 102.29 | 98.41 |
| 10 | 83.69 | 89.34 | 94.52 | 99.04 | 102.05 | 103.90 | 104.68 | 106.00 | 112.48 | 121.92 | 118.81 | 117.33 | 115.07 | 111.16 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 31.31 | 30.75 | 30.58 | 30.36 | 29.85 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 118.812 | — |
| SC2 | 0 | 8 | 82.420 | — |
| SC3 | -18 | 7 | 68.703 | — |
| SC4 | -25 | 6 | 55.849 | — |
| SC5 | -34 | 6 | 53.655 | — |
| A | 3025 mm |
|---|---|
| B | 1200 mm |
| C | 1350 mm |
| F | 1160 mm |
| G | 2000 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø80 |
| Length | 3025 mm |
|---|---|
| Width | 2000 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.