EA-DI-463GG7-A13 C
126.89 kW
Defrost: None
Product code: EA-DI-391GG7-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 68,875 m³/h |
|---|---|
| External surface | 527.3 m² |
| Inner volume | 154.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 935 kg |
| Quantity | 3 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 8,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 96.5 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EA-DI-391GG7-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 50.64 | 49.97 | 49.68 | 49.64 | 49.40 | 49.03 | 48.56 | 49.80 | 52.95 | 57.32 | 56.11 | 55.66 | 55.03 | 54.10 |
| 5 | 66.85 | 66.59 | 66.50 | 66.70 | 66.48 | 65.96 | 65.19 | 66.24 | 70.38 | 76.19 | 74.33 | 73.71 | 72.85 | 71.64 |
| 6 | 82.72 | 83.34 | 84.06 | 84.76 | 84.77 | 84.18 | 83.23 | 84.08 | 89.14 | 96.34 | 93.49 | 92.48 | 91.03 | 88.87 |
| 7 | 97.97 | 99.83 | 101.57 | 102.81 | 103.36 | 103.10 | 102.14 | 102.83 | 108.90 | 117.61 | 113.83 | 112.40 | 110.30 | 106.99 |
| 8 | 111.76 | 115.05 | 118.17 | 120.94 | 122.25 | 122.43 | 121.65 | 122.28 | 129.44 | 139.92 | 135.30 | 133.48 | 130.79 | 126.40 |
| 9 | 124.25 | 128.90 | 133.22 | 137.09 | 139.47 | 140.65 | 140.69 | 141.97 | 150.52 | 162.69 | 157.48 | 155.31 | 152.06 | 146.57 |
| 10 | 135.84 | 142.12 | 147.86 | 152.93 | 156.02 | 157.73 | 158.13 | 159.59 | 169.21 | 183.27 | 178.38 | 176.24 | 172.99 | 167.20 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 41.07 | 43.93 | 47.79 | 47.06 | 46.82 | 46.39 | 45.74 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 58.22 |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 178.382 | — |
| SC2 | 0 | 8 | 122.283 | — |
| SC3 | -18 | 7 | 103.141 | — |
| SC4 | -25 | 6 | 84.058 | — |
| SC5 | -34 | 6 | 82.966 | — |
| A | 4325 mm |
|---|---|
| B | 1100 mm |
| C | 1350 mm |
| F | 1060 mm |
| G | 1900 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 3935 mm |
| D IN | 2 x Ø35 |
| D OUT | 2 x Ø66,7 |
| Length | 4325 mm |
|---|---|
| Width | 1900 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.