EA-DR (Banana Ripnening)
- Application
- Cubic, Industrial
- Air discharge
- Single
- Refrigerants
- R134a, R22, R290, R32, R404A, R407A, R407B, R407C, R407F, R410A, R448A, R449A, R450a, R452a, R454A, R454C, R455A, R507A, R513a, R744
- Capacity
- 7.60–32.75 kW
- Fans
- ⌀450, ⌀500, ⌀630 mm
- Max. working pressure
- 25 bar
Model nomenclature
How to read the model codes of this series, with an example.
-
A
Model code (series) EA-DR = EA-DR - banana ripening unit cooler
-
B
Number of fans — Number of fans (one digit).
-
C
Fan diameter — Fan diameter in cm (two digits; x10 = mm), e.g. 30=Ø300, 63=Ø630, 91=Ø910. 45 = Ø450 mm50 = Ø500 mm63 = Ø630 mm
-
D
Dimensional data - coil size letter — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
-
E
Dimensional data - tube rows — Second letter of the dimensional data = number of tube rows (coil depth): A=2, B=3, C=4, D=5, E=6, G=8, I=10, K=12 (alphabet position + 1). A = 2 tube rowsB = 3 tube rows
-
F
Fin spacing — Nominal fin spacing in mm (1-2 digits). Karyer catalogue: 4=4.20, 6=6.00. The exact pitch is per model (e.g. 4 covers 3.8 to 4.6 mm). 4 = Fin spacing about 4 mm6 = Fin spacing about 6 mm7 = Fin spacing about 7 mm8 = Fin spacing about 8 mm10 = Fin spacing about 10 mm
-
G
Generation code — Karyer design generation letter; Karyer publishes no further decoding. A = Generation A
-
H
Fan data 07 = Ø450: 400V/3Ph/50Hz, 4-pole08 = Ø630: 400V/3Ph/50Hz, 4-pole10 = Ø500: 400V/3Ph/50Hz, 4-pole13 = Ø630: 400V/3Ph/50Hz, 4-pole
| Model | Cooling capacity [kW] i Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 % | Fin spacing [mm] | Fans | Air throw [m] | Air flow [m³/h] | Defrost | Variants |
|---|---|---|---|---|---|---|---|
| EA-DR-245EA10-A07 C | 7.60 kW | 10.0 | 2 × ⌀450 | 24 | 13,534 | None |
Variants (1) |
| EA-DR-245BB10-A07 C | 8.61 kW | 10.0 | 2 × ⌀450 | 23 | 12,760 | None |
Variants (1) |
| EA-DR-250EB10-A10 C | 12.02 kW | 10.0 | 2 × ⌀500 | 24 | 16,586 | None |
Variants (1) |
| EA-DR-350BB8-A10 C | 16.79 kW | 8.0 | 3 × ⌀500 | 24 | 23,414 | None |
Variants (1) |
| EA-DR-350EB10-A10 C | 17.41 kW | 10.0 | 3 × ⌀500 | 25 | 24,766 | None |
Variants (1) |
| EA-DR-450BB8-A10 C | 20.85 kW | 8.0 | 4 × ⌀500 | 25 | 31,206 | None |
Variants (1) |
| EA-DR-450EB10-A10 C | 21.86 kW | 10.0 | 4 × ⌀500 | 26 | 32,812 | None |
Variants (1) |
| EA-DR-363CB6-A08 C | 24.89 kW | 6.0 | 3 × ⌀630 | 42 | 47,551 | None |
Variants (1) |
| EA-DR-363CB4-A13 C | 30.81 kW | 4.2 | 3 × ⌀630 | 46 | 52,110 | None |
Variants (1) |
| EA-DR-363CB7-A13 C | 32.75 kW | 7.0 | 3 × ⌀630 | 48 | 54,028 | None |
Variants (1) |
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
Downloads
- EA-DR-245EA10-A07 C — product datasheet (PDF)
- EA-DR-245BB10-A07 C — product datasheet (PDF)
- EA-DR-250EB10-A10 C — product datasheet (PDF)
- EA-DR-350BB8-A10 C — product datasheet (PDF)
- EA-DR-350EB10-A10 C — product datasheet (PDF)
- EA-DR-450BB8-A10 C — product datasheet (PDF)
- EA-DR-450EB10-A10 C — product datasheet (PDF)
- EA-DR-363CB6-A08 C — product datasheet (PDF)
- EA-DR-363CB4-A13 C — product datasheet (PDF)
- EA-DR-363CB7-A13 C — product datasheet (PDF)
Ask about product
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.