EA-DV-180GC7-A01 C
23.36 kW
Defrost: None
Product code: EA-DV-163GE10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,407 m³/h |
|---|---|
| External surface | 79.4 m² |
| Inner volume | 33.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 257 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-DV-163GE10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.08 | 8.89 | 8.79 | 8.74 | 8.67 | 8.59 | 8.50 | 8.54 | 9.03 | 9.75 | 9.51 | 9.42 | 9.29 | 9.10 |
| 5 | 12.06 | 11.94 | 11.89 | 11.88 | 11.81 | 11.70 | 11.58 | 11.59 | 12.26 | 13.23 | 12.87 | 12.73 | 12.55 | 12.27 |
| 6 | 15.09 | 15.09 | 15.14 | 15.19 | 15.16 | 15.07 | 14.93 | 14.92 | 15.78 | 17.02 | 16.51 | 16.32 | 16.06 | 15.65 |
| 7 | 17.98 | 18.19 | 18.40 | 18.60 | 18.66 | 18.61 | 18.48 | 18.46 | 19.52 | 21.06 | 20.42 | 20.18 | 19.82 | 19.27 |
| 8 | 20.74 | 21.20 | 21.63 | 21.95 | 22.14 | 22.18 | 22.11 | 22.11 | 23.40 | 25.27 | 24.51 | 24.21 | 23.78 | 23.08 |
| 9 | 23.31 | 23.95 | 24.65 | 25.28 | 25.64 | 25.80 | 25.81 | 25.86 | 27.38 | 29.59 | 28.75 | 28.41 | 27.91 | 27.09 |
| 10 | 25.47 | 26.47 | 27.41 | 28.26 | 28.83 | 29.19 | 29.38 | 29.60 | 31.40 | 33.97 | 33.07 | 32.69 | 32.13 | 31.20 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.99 | 7.82 | 7.73 | 7.69 | 7.64 | 7.59 | 7.53 | 7.59 | 8.05 | 8.70 | 8.50 | 8.43 | 8.32 | 8.17 |
| 5 | 10.57 | 10.42 | 10.36 | 10.34 | 10.29 | 10.21 | 10.11 | 10.15 | 10.75 | 11.62 | 11.31 | 11.21 | 11.06 | 10.83 |
| 6 | 13.22 | 13.10 | 13.10 | 13.14 | 13.11 | 13.03 | 12.91 | 12.92 | 13.68 | 14.77 | 14.34 | 14.19 | 13.97 | 13.63 |
| 7 | 15.78 | 15.83 | 15.92 | 16.04 | 16.04 | 15.99 | 15.87 | 15.87 | 16.78 | 18.12 | 17.57 | 17.37 | 17.07 | 16.60 |
| 8 | 18.26 | 18.48 | 18.72 | 18.96 | 19.05 | 19.04 | 18.93 | 18.93 | 20.02 | 21.62 | 20.97 | 20.71 | 20.34 | 19.73 |
| 9 | 20.62 | 21.05 | 21.48 | 21.81 | 22.02 | 22.09 | 22.03 | 22.05 | 23.33 | 25.20 | 24.46 | 24.16 | 23.72 | 22.99 |
| 10 | 22.84 | 23.45 | 24.09 | 24.67 | 25.00 | 25.16 | 25.16 | 25.22 | 26.71 | 28.86 | 28.05 | 27.72 | 27.21 | 26.36 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 33.069 | 28.054 |
| SC2 | 0 | 8 | 22.114 | 18.925 |
| SC3 | -18 | 7 | 18.642 | 16.057 |
| SC4 | -25 | 6 | 15.139 | 13.102 |
| SC5 | -34 | 6 | 15.113 | 13.215 |
| A | 1725 mm |
|---|---|
| B | 1000 mm |
| C | 1260 mm |
| F | 960 mm |
| G | 1685 mm |
| E | 1335 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1725 mm |
|---|---|
| Width | 1685 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.