EA-DV-163GE7-A13 C
27.20 kW
Defrost: None
Product code: EA-DV-163GE7-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,022 m³/h |
|---|---|
| External surface | 109.9 m² |
| Inner volume | 33.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 259 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-DV-163GE7-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.30 | 10.18 | 10.13 | 10.13 | 10.10 | 10.05 | 9.99 | 10.09 | 10.69 | 11.57 | 11.32 | 11.22 | 11.09 | 10.89 |
| 5 | 13.58 | 13.50 | 13.54 | 13.60 | 13.59 | 13.53 | 13.43 | 13.50 | 14.31 | 15.48 | 15.09 | 14.96 | 14.77 | 14.48 |
| 6 | 16.77 | 16.93 | 17.10 | 17.27 | 17.32 | 17.27 | 17.16 | 17.21 | 18.23 | 19.70 | 19.17 | 18.97 | 18.69 | 18.26 |
| 7 | 19.84 | 20.26 | 20.65 | 21.00 | 21.11 | 21.15 | 21.07 | 21.13 | 22.37 | 24.17 | 23.50 | 23.24 | 22.86 | 22.26 |
| 8 | 22.73 | 23.36 | 24.03 | 24.62 | 24.96 | 25.11 | 25.10 | 25.19 | 26.68 | 28.86 | 28.05 | 27.73 | 27.26 | 26.49 |
| 9 | 25.15 | 26.16 | 27.10 | 27.96 | 28.53 | 28.89 | 29.08 | 29.32 | 31.08 | 33.64 | 32.74 | 32.37 | 31.81 | 30.91 |
| 10 | 27.47 | 28.82 | 30.06 | 31.17 | 31.91 | 32.40 | 32.67 | 32.98 | 35.01 | 37.99 | 37.15 | 36.80 | 36.26 | 35.37 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.06 | 8.93 | 8.88 | 8.89 | 8.87 | 8.84 | 8.80 | 8.91 | 9.48 | 10.27 | 10.07 | 9.99 | 9.89 | 9.72 |
| 5 | 11.85 | 11.77 | 11.76 | 11.80 | 11.79 | 11.74 | 11.67 | 11.76 | 12.48 | 13.52 | 13.20 | 13.09 | 12.94 | 12.70 |
| 6 | 14.69 | 14.71 | 14.78 | 14.87 | 14.90 | 14.86 | 14.76 | 14.84 | 15.72 | 17.00 | 16.56 | 16.39 | 16.16 | 15.80 |
| 7 | 17.42 | 17.61 | 17.83 | 18.05 | 18.14 | 18.12 | 18.01 | 18.08 | 19.15 | 20.70 | 20.11 | 19.89 | 19.57 | 19.05 |
| 8 | 20.03 | 20.45 | 20.86 | 21.23 | 21.37 | 21.43 | 21.36 | 21.42 | 22.69 | 24.53 | 23.81 | 23.54 | 23.12 | 22.45 |
| 9 | 22.50 | 23.10 | 23.74 | 24.31 | 24.65 | 24.78 | 24.77 | 24.86 | 26.33 | 28.47 | 27.67 | 27.33 | 26.84 | 26.03 |
| 10 | 24.63 | 25.56 | 26.43 | 27.23 | 27.75 | 28.08 | 28.20 | 28.34 | 30.03 | 32.48 | 31.59 | 31.22 | 30.65 | 29.70 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 37.151 | 31.594 |
| SC2 | 0 | 8 | 25.186 | 21.424 |
| SC3 | -18 | 7 | 21.037 | 18.099 |
| SC4 | -25 | 6 | 17.098 | 14.784 |
| SC5 | -34 | 6 | 16.830 | 14.711 |
| A | 1725 mm |
|---|---|
| B | 1000 mm |
| C | 1260 mm |
| F | 960 mm |
| G | 1685 mm |
| E | 1335 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1725 mm |
|---|---|
| Width | 1685 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.