EA-DV-263GC7-A13 C
37.54 kW
Defrost: None
Product code: EA-DV-163GI7-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,664 m³/h |
|---|---|
| External surface | 182.8 m² |
| Inner volume | 54.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 323 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-DV-163GI7-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.14 | 15.11 | 15.15 | 15.23 | 15.24 | 15.20 | 15.12 | 15.31 | 16.27 | 17.63 | 17.27 | 17.14 | 16.96 | 16.67 |
| 5 | 19.59 | 19.75 | 19.90 | 20.13 | 20.20 | 20.18 | 20.07 | 20.23 | 21.46 | 23.23 | 22.65 | 22.44 | 22.15 | 21.70 |
| 6 | 23.81 | 24.30 | 24.76 | 25.19 | 25.39 | 25.42 | 25.30 | 25.45 | 26.97 | 29.18 | 28.38 | 28.08 | 27.64 | 26.94 |
| 7 | 27.80 | 28.70 | 29.52 | 30.12 | 30.53 | 30.70 | 30.67 | 30.83 | 32.67 | 35.35 | 34.35 | 33.96 | 33.39 | 32.45 |
| 8 | 31.50 | 32.71 | 33.95 | 35.03 | 35.71 | 36.06 | 36.12 | 36.34 | 38.52 | 41.69 | 40.56 | 40.09 | 39.39 | 38.20 |
| 9 | 34.62 | 36.40 | 38.03 | 39.49 | 40.48 | 41.09 | 41.41 | 41.81 | 44.38 | 48.11 | 46.87 | 46.33 | 45.52 | 44.09 |
| 10 | 37.59 | 39.87 | 41.96 | 43.81 | 45.09 | 45.91 | 46.36 | 46.86 | 49.75 | 53.97 | 52.78 | 52.24 | 51.42 | 49.95 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.63 | 12.54 | 12.54 | 12.61 | 12.61 | 12.58 | 12.51 | 12.76 | 13.59 | 14.76 | 14.48 | 14.39 | 14.27 | 14.09 |
| 5 | 16.24 | 16.25 | 16.34 | 16.47 | 16.51 | 16.46 | 16.35 | 16.56 | 17.59 | 19.07 | 18.60 | 18.44 | 18.20 | 17.85 |
| 6 | 19.86 | 20.02 | 20.25 | 20.46 | 20.56 | 20.53 | 20.40 | 20.56 | 21.80 | 23.61 | 22.94 | 22.69 | 22.33 | 21.74 |
| 7 | 23.28 | 23.70 | 24.12 | 24.53 | 24.71 | 24.71 | 24.58 | 24.72 | 26.18 | 28.33 | 27.48 | 27.14 | 26.64 | 25.82 |
| 8 | 26.54 | 27.26 | 27.94 | 28.56 | 28.88 | 28.98 | 28.81 | 28.96 | 30.65 | 33.13 | 32.14 | 31.72 | 31.10 | 30.07 |
| 9 | 29.59 | 30.68 | 31.55 | 32.42 | 32.94 | 33.15 | 33.11 | 33.27 | 35.23 | 38.06 | 36.94 | 36.44 | 35.70 | 34.51 |
| 10 | 32.44 | 33.75 | 35.07 | 36.25 | 37.00 | 37.37 | 37.41 | 37.63 | 39.84 | 43.05 | 41.81 | 41.25 | 40.39 | 39.05 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 52.776 | 41.812 |
| SC2 | 0 | 8 | 36.340 | 28.957 |
| SC3 | -18 | 7 | 30.317 | 24.624 |
| SC4 | -25 | 6 | 24.761 | 20.246 |
| SC5 | -34 | 6 | 23.948 | 19.917 |
| A | 1725 mm |
|---|---|
| B | 1200 mm |
| C | 1260 mm |
| F | 1160 mm |
| G | 1885 mm |
| E | 1335 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1885 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.