EA-DV-263GC4-A08 C
46.03 kW
Defrost: None
Product code: EA-DV-263GE10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 32,814 m³/h |
|---|---|
| External surface | 158.7 m² |
| Inner volume | 66.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 476 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EA-DV-263GE10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 18.29 | 17.89 | 17.66 | 17.55 | 17.40 | 17.23 | 17.06 | 17.13 | 18.12 | 19.56 | 19.06 | 18.88 | 18.63 | 18.24 |
| 5 | 24.34 | 24.05 | 23.90 | 23.85 | 23.70 | 23.48 | 23.23 | 23.24 | 24.60 | 26.54 | 25.80 | 25.53 | 25.16 | 24.60 |
| 6 | 30.50 | 30.42 | 30.46 | 30.52 | 30.45 | 30.25 | 29.96 | 29.93 | 31.66 | 34.13 | 33.11 | 32.73 | 32.19 | 31.37 |
| 7 | 36.39 | 36.70 | 37.05 | 37.41 | 37.49 | 37.37 | 37.08 | 37.03 | 39.16 | 42.24 | 40.95 | 40.46 | 39.75 | 38.63 |
| 8 | 42.02 | 42.82 | 43.58 | 44.16 | 44.50 | 44.55 | 44.38 | 44.37 | 46.94 | 50.68 | 49.15 | 48.56 | 47.68 | 46.28 |
| 9 | 47.26 | 48.40 | 49.68 | 50.90 | 51.56 | 51.83 | 51.81 | 51.88 | 54.93 | 59.36 | 57.67 | 56.98 | 55.97 | 54.31 |
| 10 | 51.72 | 53.56 | 55.30 | 56.91 | 57.96 | 58.63 | 58.98 | 59.38 | 63.01 | 68.15 | 66.33 | 65.57 | 64.43 | 62.55 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 16.08 | 15.71 | 15.51 | 15.44 | 15.33 | 15.22 | 15.09 | 15.21 | 16.13 | 17.44 | 17.04 | 16.89 | 16.68 | 16.37 |
| 5 | 21.30 | 20.97 | 20.81 | 20.76 | 20.64 | 20.47 | 20.28 | 20.35 | 21.55 | 23.29 | 22.68 | 22.47 | 22.16 | 21.71 |
| 6 | 26.66 | 26.38 | 26.34 | 26.39 | 26.31 | 26.14 | 25.90 | 25.92 | 27.43 | 29.61 | 28.76 | 28.44 | 28.00 | 27.32 |
| 7 | 31.88 | 31.88 | 32.02 | 32.23 | 32.21 | 32.07 | 31.83 | 31.82 | 33.66 | 36.33 | 35.23 | 34.82 | 34.22 | 33.28 |
| 8 | 36.92 | 37.26 | 37.67 | 38.10 | 38.26 | 38.20 | 37.98 | 37.96 | 40.15 | 43.35 | 42.03 | 41.52 | 40.77 | 39.54 |
| 9 | 41.75 | 42.50 | 43.25 | 43.87 | 44.25 | 44.34 | 44.20 | 44.22 | 46.79 | 50.54 | 49.04 | 48.44 | 47.55 | 46.09 |
| 10 | 46.31 | 47.39 | 48.57 | 49.64 | 50.24 | 50.51 | 50.49 | 50.60 | 53.56 | 57.88 | 56.25 | 55.57 | 54.55 | 52.83 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 66.327 | 56.249 |
| SC2 | 0 | 8 | 44.370 | 37.955 |
| SC3 | -18 | 7 | 37.467 | 32.247 |
| SC4 | -25 | 6 | 30.458 | 26.340 |
| SC5 | -34 | 6 | 30.517 | 26.640 |
| A | 3025 mm |
|---|---|
| B | 1000 mm |
| C | 1260 mm |
| F | 960 mm |
| G | 1685 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø66,7 |
| Length | 3025 mm |
|---|---|
| Width | 1685 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.