EA-130AC8-C05 C
1.66 kW
Defrost: None
Product code: EA-130AC10-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,222 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 4.9 m² |
| Inner volume | 2.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 18 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 120 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 41.0 dB(A) |
|---|---|
| Sound power | 62.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø12,7 |
| EA-130AC10-C05 C | None |
|---|---|
| EA-130AC10-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.56 | 0.56 | 0.56 | 0.56 | 0.56 | 0.56 | 0.55 | 0.56 | 0.60 | 0.65 | 0.63 | 0.62 | 0.62 | 0.60 |
| 5 | 0.73 | 0.74 | 0.76 | 0.77 | 0.77 | 0.77 | 0.77 | 0.78 | 0.82 | 0.89 | 0.87 | 0.86 | 0.85 | 0.84 |
| 6 | 0.90 | 0.93 | 0.95 | 0.98 | 0.99 | 1.00 | 0.99 | 1.00 | 1.07 | 1.15 | 1.12 | 1.11 | 1.09 | 1.07 |
| 7 | 1.06 | 1.11 | 1.15 | 1.19 | 1.21 | 1.23 | 1.23 | 1.24 | 1.32 | 1.43 | 1.39 | 1.38 | 1.35 | 1.32 |
| 8 | 1.21 | 1.28 | 1.34 | 1.40 | 1.44 | 1.46 | 1.47 | 1.49 | 1.58 | 1.71 | 1.67 | 1.65 | 1.63 | 1.58 |
| 9 | 1.34 | 1.43 | 1.52 | 1.59 | 1.64 | 1.68 | 1.70 | 1.73 | 1.84 | 2.00 | 1.95 | 1.93 | 1.90 | 1.85 |
| 10 | 1.46 | 1.57 | 1.67 | 1.77 | 1.83 | 1.87 | 1.91 | 1.94 | 2.07 | 2.25 | 2.21 | 2.19 | 2.16 | 2.11 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 2.211 |
| SC2 | 0 | 8 | 1.487 |
| SC3 | -18 | 7 | 1.200 |
| SC4 | -25 | 6 | 0.954 |
| SC5 | -34 | 6 | 0.905 |
| A | 777 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E | 455 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø12,7 |
| Length | 777 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.