EA-130AC4-C05 C
2.15 kW
Defrost: None
Product code: EA-130AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,242 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 7.3 m² |
| Inner volume | 3.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 25 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.5 dB(A) |
| Energy class | B |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EA-130AE10-C01 C | None |
|---|---|
| EA-130AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.84 | 0.83 | 0.82 | 0.82 | 0.81 | 0.81 | 0.80 | 0.81 | 0.86 | 0.93 | 0.91 | 0.91 | 0.90 | 0.88 |
| 5 | 1.12 | 1.11 | 1.11 | 1.11 | 1.10 | 1.10 | 1.08 | 1.10 | 1.16 | 1.26 | 1.23 | 1.22 | 1.20 | 1.18 |
| 6 | 1.40 | 1.40 | 1.41 | 1.42 | 1.42 | 1.41 | 1.40 | 1.41 | 1.49 | 1.61 | 1.56 | 1.54 | 1.52 | 1.48 |
| 7 | 1.67 | 1.69 | 1.71 | 1.73 | 1.74 | 1.74 | 1.72 | 1.73 | 1.83 | 1.98 | 1.92 | 1.90 | 1.86 | 1.81 |
| 8 | 1.94 | 1.98 | 2.02 | 2.05 | 2.07 | 2.08 | 2.07 | 2.07 | 2.19 | 2.37 | 2.30 | 2.27 | 2.22 | 2.15 |
| 9 | 2.20 | 2.26 | 2.32 | 2.37 | 2.40 | 2.42 | 2.41 | 2.42 | 2.57 | 2.77 | 2.69 | 2.65 | 2.60 | 2.51 |
| 10 | 2.44 | 2.53 | 2.62 | 2.69 | 2.74 | 2.76 | 2.76 | 2.78 | 2.94 | 3.18 | 3.09 | 3.05 | 2.99 | 2.88 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.089 |
| SC2 | 0 | 8 | 2.073 |
| SC3 | -18 | 7 | 1.738 |
| SC4 | -25 | 6 | 1.407 |
| SC5 | -34 | 6 | 1.401 |
| A | 777 mm |
|---|---|
| B | 573 mm |
| C | 445 mm |
| F | 395 mm |
| E | 455 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 777 mm |
|---|---|
| Width | 573 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.