EA-130AC4-C01 C
2.35 kW
Defrost: None
Product code: EA-130BE10-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,236 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 9.6 m² |
| Inner volume | 4.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 25 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 120 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 41.0 dB(A) |
|---|---|
| Sound power | 62.0 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EA-130BE10-C05 C | None |
|---|---|
| EA-130BE10-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.92 | 0.92 | 0.92 | 0.92 | 0.92 | 0.91 | 0.91 | 0.93 | 0.98 | 1.07 | 1.05 | 1.04 | 1.03 | 1.01 |
| 5 | 1.21 | 1.21 | 1.22 | 1.23 | 1.23 | 1.23 | 1.22 | 1.24 | 1.31 | 1.42 | 1.39 | 1.37 | 1.36 | 1.33 |
| 6 | 1.48 | 1.50 | 1.53 | 1.55 | 1.56 | 1.56 | 1.55 | 1.57 | 1.66 | 1.80 | 1.75 | 1.73 | 1.70 | 1.66 |
| 7 | 1.75 | 1.79 | 1.83 | 1.87 | 1.89 | 1.90 | 1.90 | 1.91 | 2.03 | 2.19 | 2.13 | 2.10 | 2.07 | 2.01 |
| 8 | 2.01 | 2.07 | 2.14 | 2.19 | 2.23 | 2.25 | 2.25 | 2.26 | 2.40 | 2.60 | 2.53 | 2.49 | 2.45 | 2.37 |
| 9 | 2.26 | 2.35 | 2.44 | 2.52 | 2.56 | 2.59 | 2.60 | 2.62 | 2.78 | 3.01 | 2.93 | 2.90 | 2.84 | 2.75 |
| 10 | 2.49 | 2.61 | 2.73 | 2.83 | 2.90 | 2.94 | 2.95 | 2.99 | 3.17 | 3.43 | 3.34 | 3.30 | 3.24 | 3.13 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.344 |
| SC2 | 0 | 8 | 2.264 |
| SC3 | -18 | 7 | 1.882 |
| SC4 | -25 | 6 | 1.525 |
| SC5 | -34 | 6 | 1.490 |
| A | 907 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E | 585 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 907 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.