EA-230BC10-C01 C
3.75 kW
Defrost: None
Product code: EA-135AE8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,220 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 12.7 m² |
| Inner volume | 4.9 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 34 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-135AE8-C01 C | None |
|---|---|
| EA-135AE8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.43 | 1.40 | 1.39 | 1.38 | 1.37 | 1.36 | 1.34 | 1.38 | 1.46 | 1.57 | 1.54 | 1.53 | 1.51 | 1.48 |
| 5 | 1.91 | 1.90 | 1.89 | 1.89 | 1.88 | 1.86 | 1.83 | 1.86 | 1.98 | 2.14 | 2.09 | 2.07 | 2.04 | 2.01 |
| 6 | 2.40 | 2.41 | 2.42 | 2.44 | 2.43 | 2.41 | 2.38 | 2.41 | 2.55 | 2.75 | 2.67 | 2.64 | 2.60 | 2.54 |
| 7 | 2.88 | 2.92 | 2.97 | 3.00 | 3.01 | 3.00 | 2.97 | 2.98 | 3.16 | 3.41 | 3.29 | 3.25 | 3.19 | 3.09 |
| 8 | 3.36 | 3.44 | 3.51 | 3.57 | 3.61 | 3.61 | 3.58 | 3.59 | 3.80 | 4.10 | 3.96 | 3.90 | 3.82 | 3.69 |
| 9 | 3.79 | 3.92 | 4.04 | 4.15 | 4.21 | 4.22 | 4.20 | 4.22 | 4.46 | 4.82 | 4.66 | 4.59 | 4.49 | 4.33 |
| 10 | 4.19 | 4.37 | 4.53 | 4.68 | 4.77 | 4.83 | 4.83 | 4.86 | 5.14 | 5.55 | 5.37 | 5.30 | 5.18 | 4.99 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.373 |
| SC2 | 0 | 8 | 3.592 |
| SC3 | -18 | 7 | 3.011 |
| SC4 | -25 | 6 | 2.424 |
| SC5 | -34 | 6 | 2.408 |
| A | 857 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E | 535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 857 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.