EA-530AC10-C05 C
8.08 kW
Defrost: None
Product code: EA-145AC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,978 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 26.6 m² |
| Inner volume | 5.8 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 47 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø22 |
| EA-145AC4-C01 C | None |
|---|---|
| EA-145AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.86 | 2.95 | 3.01 | 3.07 | 3.09 | 3.08 | 3.06 | 3.13 | 3.32 | 3.58 | 3.50 | 3.47 | 3.42 | 3.35 |
| 5 | 3.72 | 3.91 | 4.07 | 4.21 | 4.28 | 4.29 | 4.28 | 4.35 | 4.63 | 5.01 | 4.89 | 4.85 | 4.78 | 4.70 |
| 6 | 4.43 | 4.71 | 4.96 | 5.15 | 5.29 | 5.38 | 5.43 | 5.54 | 5.89 | 6.41 | 6.28 | 6.23 | 6.17 | 6.06 |
| 7 | 5.04 | 5.39 | 5.74 | 6.05 | 6.27 | 6.41 | 6.48 | 6.61 | 7.03 | 7.65 | 7.50 | 7.44 | 7.34 | 7.19 |
| 8 | ≈ 5.48 | 6.05 | 6.51 | 6.92 | 7.22 | 7.42 | 7.54 | 7.69 | 8.19 | 8.92 | 8.74 | 8.66 | 8.54 | 8.34 |
| 9 | ≈ 6.04 | 6.65 | 7.23 | 7.75 | 8.15 | 8.43 | 8.60 | 8.78 | 9.36 | 10.20 | 10.00 | 9.91 | 9.77 | 9.53 |
| 10 | ≈ 5.70 | ≈ 7.20 | 7.90 | 8.55 | 9.05 | 9.41 | 9.64 | 9.87 | 10.52 | 11.47 | 11.27 | 11.17 | 11.01 | 10.73 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.271 |
| SC2 | 0 | 8 | 7.693 |
| SC3 | -18 | 7 | 6.144 |
| SC4 | -25 | 6 | 4.961 |
| SC5 | -34 | 6 | 4.495 |
| A | 1067 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E | 735 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø22 |
| Length | 1067 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.