EA-235AC4-C01 C
7.62 kW
Defrost: None
Product code: EA-145AE8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,876 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 22.2 m² |
| Inner volume | 8.6 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 54 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-145AE8-C01 C | None |
|---|---|
| EA-145AE8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.78 | 2.74 | 2.71 | 2.69 | 2.66 | 2.63 | 2.59 | 2.64 | 2.79 | 3.01 | 2.93 | 2.90 | 2.86 | 2.81 |
| 5 | 3.75 | 3.74 | 3.74 | 3.74 | 3.72 | 3.67 | 3.61 | 3.66 | 3.88 | 4.19 | 4.07 | 4.04 | 3.98 | 3.90 |
| 6 | 4.71 | 4.76 | 4.82 | 4.86 | 4.86 | 4.82 | 4.75 | 4.80 | 5.08 | 5.48 | 5.30 | 5.24 | 5.15 | 5.03 |
| 7 | 5.66 | 5.80 | 5.92 | 6.00 | 6.05 | 6.03 | 5.97 | 6.01 | 6.36 | 6.86 | 6.62 | 6.54 | 6.41 | 6.21 |
| 8 | 6.54 | 6.77 | 6.98 | 7.16 | 7.26 | 7.28 | 7.23 | 7.27 | 7.70 | 8.32 | 8.04 | 7.92 | 7.76 | 7.49 |
| 9 | 7.30 | 7.62 | 7.91 | 8.18 | 8.35 | 8.45 | 8.46 | 8.55 | 9.06 | 9.80 | 9.49 | 9.36 | 9.16 | 8.84 |
| 10 | 7.99 | 8.42 | 8.81 | 9.12 | 9.34 | 9.48 | 9.54 | 9.65 | 10.25 | 11.11 | 10.84 | 10.72 | 10.53 | 10.22 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.842 |
| SC2 | 0 | 8 | 7.273 |
| SC3 | -18 | 7 | 6.028 |
| SC4 | -25 | 6 | 4.815 |
| SC5 | -34 | 6 | 4.728 |
| A | 1067 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E | 735 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1067 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.