EA-630BC10-C01 C
9.62 kW
Defrost: None
Product code: EA-150AE10-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,690 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 23.7 m² |
| Inner volume | 11.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 64 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 710 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-150AE10-C09 C | None |
|---|---|
| EA-150AE10-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.46 | 3.41 | 3.37 | 3.35 | 3.31 | 3.27 | 3.21 | 3.24 | 3.42 | 3.69 | 3.58 | 3.54 | 3.48 | 3.40 |
| 5 | 4.66 | 4.66 | 4.67 | 4.68 | 4.66 | 4.61 | 4.54 | 4.57 | 4.84 | 5.21 | 5.05 | 5.00 | 4.92 | 4.80 |
| 6 | 5.83 | 5.92 | 6.00 | 6.07 | 6.09 | 6.06 | 5.99 | 6.03 | 6.38 | 6.88 | 6.66 | 6.58 | 6.46 | 6.29 |
| 7 | 6.98 | 7.17 | 7.35 | 7.50 | 7.56 | 7.57 | 7.53 | 7.57 | 8.01 | 8.65 | 8.37 | 8.26 | 8.10 | 7.85 |
| 8 | 8.03 | 8.34 | 8.63 | 8.89 | 9.05 | 9.12 | 9.10 | 9.16 | 9.70 | 10.50 | 10.17 | 10.04 | 9.85 | 9.53 |
| 9 | 8.94 | 9.36 | 9.75 | 10.11 | 10.32 | 10.47 | 10.55 | 10.67 | 11.33 | 12.31 | 12.01 | 11.86 | 11.64 | 11.27 |
| 10 | 9.77 | 10.33 | 10.79 | 11.25 | 11.56 | 11.77 | 11.89 | 12.05 | 12.80 | 13.90 | 13.60 | 13.47 | 13.26 | 12.91 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.601 |
| SC2 | 0 | 8 | 9.157 |
| SC3 | -18 | 7 | 7.524 |
| SC4 | -25 | 6 | 5.999 |
| SC5 | -34 | 6 | 5.853 |
| A | 1237 mm |
|---|---|
| B | 640 mm |
| C | 685 mm |
| F | 445 mm |
| E | 885 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1237 mm |
|---|---|
| Width | 640 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.