EA-445AE8-C01 C
30.93 kW
Defrost: None
Product code: EA-163GE4-C13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 17,455 m³/h |
|---|---|
| Air throw | 41 m |
| External surface | 162.9 m² |
| Inner volume | 33.1 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 186 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.9 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-163GE4-C13 C | None |
|---|---|
| EA-163GE4-C13 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.92 | 11.86 | 11.87 | 11.92 | 11.92 | 11.90 | 11.86 | 11.99 | 12.73 | 13.79 | 13.52 | 13.42 | 13.27 | 13.06 |
| 5 | 15.63 | 15.73 | 15.85 | 15.98 | 15.99 | 15.96 | 15.88 | 15.98 | 16.96 | 18.35 | 17.93 | 17.78 | 17.57 | 17.26 |
| 6 | 19.21 | 19.60 | 19.96 | 20.27 | 20.39 | 20.35 | 20.26 | 20.34 | 21.56 | 23.31 | 22.71 | 22.49 | 22.18 | 21.70 |
| 7 | 22.59 | 23.25 | 23.93 | 24.51 | 24.83 | 24.95 | 24.91 | 25.01 | 26.49 | 28.65 | 27.87 | 27.57 | 27.14 | 26.46 |
| 8 | 25.38 | 26.47 | 27.46 | 28.36 | 28.94 | 29.30 | 29.49 | 29.75 | 31.58 | 34.24 | 33.32 | 32.96 | 32.43 | 31.57 |
| 9 | 28.01 | 29.50 | 30.85 | 32.04 | 32.84 | 33.35 | 33.62 | 33.93 | 36.03 | 39.11 | 38.26 | 37.91 | 37.39 | 36.53 |
| 10 | 30.44 | 32.37 | 34.12 | 35.64 | 36.71 | 37.38 | 37.78 | 38.17 | 40.53 | 44.00 | 43.06 | 42.67 | 42.07 | 41.07 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.34 | 10.26 | 10.25 | 10.30 | 10.31 | 10.30 | 10.27 | 10.45 | 11.11 | 12.07 | 11.86 | 11.78 | 11.67 | 11.50 |
| 5 | 13.49 | 13.45 | 13.51 | 13.61 | 13.63 | 13.60 | 13.53 | 13.69 | 14.54 | 15.76 | 15.42 | 15.30 | 15.14 | 14.89 |
| 6 | 16.60 | 16.76 | 16.94 | 17.13 | 17.19 | 17.15 | 17.05 | 17.19 | 18.23 | 19.73 | 19.23 | 19.05 | 18.79 | 18.39 |
| 7 | 19.60 | 20.01 | 20.40 | 20.74 | 20.85 | 20.86 | 20.76 | 20.88 | 22.12 | 23.92 | 23.26 | 23.00 | 22.63 | 22.05 |
| 8 | 22.43 | 23.06 | 23.71 | 24.27 | 24.58 | 24.68 | 24.62 | 24.73 | 26.19 | 28.34 | 27.52 | 27.19 | 26.71 | 25.94 |
| 9 | 24.84 | 25.83 | 26.75 | 27.58 | 28.11 | 28.40 | 28.52 | 28.70 | 30.40 | 32.88 | 31.94 | 31.55 | 30.97 | 30.02 |
| 10 | 27.11 | 28.44 | 29.65 | 30.72 | 31.41 | 31.83 | 32.01 | 32.29 | 34.26 | 37.14 | 36.26 | 35.88 | 35.30 | 34.22 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 43.064 | 36.260 |
| SC2 | 0 | 8 | 29.746 | 24.731 |
| SC3 | -18 | 7 | 24.668 | 20.821 |
| SC4 | -25 | 6 | 19.955 | 16.942 |
| SC5 | -34 | 6 | 19.317 | 16.653 |
| A | 1715 mm |
|---|---|
| B | 1000 mm |
| C | 1185 mm |
| F | 960 mm |
| G | 1030 mm |
| E | 1335 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1715 mm |
|---|---|
| Width | 1110 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.