Skip to Content

Unit cooler EA-180GD7-C01 C

Unit cooler EA-180GD7-C01 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-180GD7-C01 C

Cooling capacity i
25.19 kW
Air flow
20,556 m³/h
Fin spacing
7.0 mm
Air throw
38 m
Fans
1 × ⌀800 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA — EA - general-purpose unit cooler
  • B
    Number of fans: 1 — Number of fans (one digit).
  • C
    Fan diameter: 80 — Ø800 mm
  • D
    Dimensional data - coil size letter: G — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: D — 5 tube rows
  • F
    Fin spacing: 7 — Fin spacing about 7 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 01 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole; Ø630: 230V/1Ph/50Hz, 6-pole; Ø800: 400V/3Ph/50Hz, 6-pole

Data

Evaporator
Air flow 20,556 m³/h
Air throw 38 m
External surface 109.9 m²
Inner volume 34.6 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 215 kg
Fans
Quantity 1
Diameter 800 mm
Speed 900 rpm
Power 1,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 80.0 dB(A)
Energy class D
Connections
Inlet Ø28
Outlet Ø42
Defrost
EA-180GD7-C01 C None
EA-180GD7-C01 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
24.040 kW
Low speed (Y)
19.835 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 9.67 9.50 9.42 9.40 9.35 9.29 9.23 9.33 9.88 10.69 10.46 10.38 10.26 10.08
5 12.90 12.77 12.74 12.75 12.70 12.60 12.48 12.59 13.36 14.44 14.09 13.97 13.79 13.50
6 16.12 16.18 16.27 16.37 16.34 16.24 16.09 16.17 17.14 18.51 17.99 17.81 17.56 17.18
7 19.23 19.55 19.84 20.10 20.18 20.12 19.97 20.00 21.18 22.87 22.19 21.94 21.59 21.03
8 22.18 22.72 23.29 23.77 24.01 24.06 23.96 24.04 25.45 27.49 26.66 26.35 25.88 25.14
9 24.70 25.60 26.45 27.21 27.70 27.99 28.06 28.19 29.86 32.29 31.34 30.97 30.41 29.50
10 27.04 28.28 29.41 30.42 31.08 31.48 31.67 31.95 33.92 36.80 35.94 35.59 35.05 33.98

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 8.31 8.16 8.09 8.08 8.06 8.02 7.98 8.15 8.64 9.37 9.19 9.12 9.03 8.89
5 10.97 10.85 10.80 10.81 10.77 10.70 10.61 10.76 11.44 12.39 12.11 12.02 11.89 11.70
6 13.73 13.68 13.67 13.72 13.70 13.61 13.48 13.61 14.43 15.61 15.20 15.06 14.85 14.55
7 16.42 16.51 16.64 16.77 16.79 16.70 16.55 16.64 17.63 19.05 18.49 18.29 17.99 17.54
8 19.02 19.31 19.60 19.87 19.97 19.92 19.77 19.84 21.00 22.67 21.96 21.70 21.30 20.68
9 21.49 22.04 22.46 22.91 23.13 23.16 23.04 23.12 24.47 26.44 25.60 25.27 24.78 24.00
10 23.78 24.49 25.23 25.91 26.32 26.44 26.38 26.48 28.03 30.29 29.37 28.98 28.41 27.48

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 35.94329.371
SC2 0 8 24.04019.835
SC3 -18 7 20.15216.793
SC4 -25 6 16.27313.665
SC5 -34 6 16.15213.735

Dimensions

Dimension drawing of EA-180GD7-C01 C
Dimension drawing
Dimensions as drawn
A 1715 mm
B 1000 mm
C 1430 mm
F 960 mm
G 1065 mm
E 1335 mm
D IN 1 x Ø28
D OUT 1 x Ø42
Overall [mm]
Length 1715 mm
Width 1100 mm
Height 1430 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.