EA-135AC8-C01 C
2.98 kW
Defrost: None
Product code: EA-230AC10-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,392 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 9.3 m² |
| Inner volume | 4.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 26 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EA-230AC10-C05 C | None |
|---|---|
| EA-230AC10-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.08 | 1.07 | 1.07 | 1.07 | 1.06 | 1.06 | 1.04 | 1.06 | 1.13 | 1.22 | 1.18 | 1.17 | 1.16 | 1.13 |
| 5 | 1.44 | 1.45 | 1.46 | 1.47 | 1.47 | 1.46 | 1.45 | 1.47 | 1.56 | 1.68 | 1.64 | 1.62 | 1.60 | 1.57 |
| 6 | 1.79 | 1.82 | 1.85 | 1.88 | 1.90 | 1.90 | 1.88 | 1.90 | 2.02 | 2.18 | 2.12 | 2.10 | 2.06 | 2.02 |
| 7 | 2.13 | 2.20 | 2.25 | 2.30 | 2.34 | 2.35 | 2.34 | 2.36 | 2.51 | 2.71 | 2.63 | 2.60 | 2.56 | 2.48 |
| 8 | 2.45 | 2.55 | 2.64 | 2.73 | 2.78 | 2.81 | 2.81 | 2.84 | 3.01 | 3.26 | 3.17 | 3.13 | 3.08 | 2.99 |
| 9 | 2.74 | 2.87 | 3.00 | 3.12 | 3.20 | 3.26 | 3.29 | 3.32 | 3.52 | 3.82 | 3.72 | 3.68 | 3.61 | 3.51 |
| 10 | 2.99 | 3.17 | 3.33 | 3.48 | 3.57 | 3.65 | 3.69 | 3.75 | 3.98 | 4.33 | 4.25 | 4.21 | 4.15 | 4.04 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.247 |
| SC2 | 0 | 8 | 2.837 |
| SC3 | -18 | 7 | 2.320 |
| SC4 | -25 | 6 | 1.853 |
| SC5 | -34 | 6 | 1.797 |
| A | 1157 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 417.5 mm |
| E | 835 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1157 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.