EA-135AC7-C01 C
3.30 kW
Defrost: None
Product code: EA-230AC8-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,319 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 11.3 m² |
| Inner volume | 4.3 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 27 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EA-230AC8-C05 C | None |
|---|---|
| EA-230AC8-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.19 | 1.18 | 1.19 | 1.19 | 1.19 | 1.18 | 1.17 | 1.19 | 1.26 | 1.37 | 1.34 | 1.32 | 1.31 | 1.28 |
| 5 | 1.57 | 1.59 | 1.61 | 1.62 | 1.63 | 1.62 | 1.61 | 1.63 | 1.73 | 1.88 | 1.83 | 1.81 | 1.79 | 1.76 |
| 6 | 1.94 | 1.99 | 2.03 | 2.08 | 2.09 | 2.10 | 2.09 | 2.11 | 2.24 | 2.42 | 2.35 | 2.33 | 2.29 | 2.24 |
| 7 | 2.30 | 2.39 | 2.47 | 2.54 | 2.57 | 2.59 | 2.59 | 2.61 | 2.77 | 3.00 | 2.91 | 2.88 | 2.83 | 2.75 |
| 8 | 2.63 | 2.76 | 2.88 | 2.98 | 3.05 | 3.09 | 3.10 | 3.13 | 3.32 | 3.60 | 3.50 | 3.46 | 3.40 | 3.29 |
| 9 | 2.92 | 3.08 | 3.24 | 3.38 | 3.46 | 3.53 | 3.56 | 3.61 | 3.84 | 4.18 | 4.09 | 4.05 | 3.98 | 3.85 |
| 10 | 3.18 | 3.39 | 3.59 | 3.74 | 3.87 | 3.95 | 4.00 | 4.07 | 4.33 | 4.70 | 4.61 | 4.57 | 4.50 | 4.37 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.610 |
| SC2 | 0 | 8 | 3.130 |
| SC3 | -18 | 7 | 2.549 |
| SC4 | -25 | 6 | 2.033 |
| SC5 | -34 | 6 | 1.951 |
| A | 1157 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 417.5 mm |
| E | 835 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1157 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.