EA-230AC6-C01 C
3.93 kW
Defrost: None
Product code: EA-230AE10-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,099 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 14.0 m² |
| Inner volume | 6.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 30 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-230AE10-C05 C | None |
|---|---|
| EA-230AE10-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.53 | 1.52 | 1.52 | 1.52 | 1.52 | 1.50 | 1.49 | 1.53 | 1.63 | 1.77 | 1.74 | 1.72 | 1.70 | 1.67 |
| 5 | 2.00 | 2.01 | 2.03 | 2.04 | 2.05 | 2.03 | 2.01 | 2.05 | 2.18 | 2.36 | 2.30 | 2.28 | 2.25 | 2.21 |
| 6 | 2.47 | 2.51 | 2.55 | 2.58 | 2.60 | 2.59 | 2.57 | 2.60 | 2.76 | 2.99 | 2.90 | 2.86 | 2.81 | 2.74 |
| 7 | 2.92 | 2.99 | 3.06 | 3.13 | 3.16 | 3.17 | 3.15 | 3.18 | 3.37 | 3.65 | 3.53 | 3.48 | 3.41 | 3.30 |
| 8 | 3.36 | 3.47 | 3.58 | 3.67 | 3.73 | 3.75 | 3.74 | 3.77 | 4.00 | 4.32 | 4.19 | 4.13 | 4.04 | 3.90 |
| 9 | 3.76 | 3.93 | 4.08 | 4.22 | 4.30 | 4.34 | 4.33 | 4.38 | 4.64 | 5.01 | 4.87 | 4.80 | 4.69 | 4.52 |
| 10 | 4.13 | 4.34 | 4.54 | 4.71 | 4.83 | 4.91 | 4.93 | 4.98 | 5.27 | 5.70 | 5.54 | 5.47 | 5.35 | 5.15 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.543 |
| SC2 | 0 | 8 | 3.773 |
| SC3 | -18 | 7 | 3.147 |
| SC4 | -25 | 6 | 2.545 |
| SC5 | -34 | 6 | 2.480 |
| A | 1157 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 417.5 mm |
| E | 835 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1157 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.