EA-140AG10-C01 C
5.44 kW
Defrost: None
Product code: EA-230BE6-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,191 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 27.2 m² |
| Inner volume | 7.6 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 37 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-230BE6-C05 C | None |
|---|---|
| EA-230BE6-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.21 | 2.20 | 2.21 | 2.22 | 2.22 | 2.21 | 2.19 | 2.25 | 2.40 | 2.61 | 2.56 | 2.54 | 2.53 | 2.50 |
| 5 | 2.86 | 2.87 | 2.90 | 2.92 | 2.93 | 2.92 | 2.89 | 2.94 | 3.13 | 3.40 | 3.31 | 3.28 | 3.23 | 3.17 |
| 6 | 3.50 | 3.55 | 3.60 | 3.65 | 3.67 | 3.67 | 3.63 | 3.68 | 3.90 | 4.22 | 4.09 | 4.04 | 3.97 | 3.85 |
| 7 | 4.14 | 4.21 | 4.30 | 4.39 | 4.43 | 4.43 | 4.40 | 4.44 | 4.70 | 5.08 | 4.92 | 4.85 | 4.75 | 4.58 |
| 8 | 4.73 | 4.87 | 5.00 | 5.13 | 5.19 | 5.20 | 5.18 | 5.22 | 5.52 | 5.97 | 5.78 | 5.69 | 5.57 | 5.35 |
| 9 | 5.28 | 5.48 | 5.68 | 5.85 | 5.95 | 5.99 | 5.97 | 6.01 | 6.36 | 6.87 | 6.66 | 6.56 | 6.41 | 6.15 |
| 10 | 5.78 | 6.04 | 6.29 | 6.52 | 6.66 | 6.74 | 6.75 | 6.80 | 7.20 | 7.77 | 7.54 | 7.43 | 7.25 | 6.95 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.538 |
| SC2 | 0 | 8 | 5.217 |
| SC3 | -18 | 7 | 4.407 |
| SC4 | -25 | 6 | 3.598 |
| SC5 | -34 | 6 | 3.515 |
| A | 1357 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1357 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.