EA-330AE8-C01 C
7.27 kW
Defrost: None
Product code: EA-235AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,813 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 21.9 m² |
| Inner volume | 6.6 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 48 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-235AC6-C01 C | None |
|---|---|
| EA-235AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.65 | 2.62 | 2.60 | 2.60 | 2.58 | 2.56 | 2.53 | 2.57 | 2.72 | 2.94 | 2.87 | 2.84 | 2.81 | 2.75 |
| 5 | 3.54 | 3.56 | 3.58 | 3.59 | 3.58 | 3.56 | 3.51 | 3.56 | 3.78 | 4.08 | 3.97 | 3.94 | 3.89 | 3.82 |
| 6 | 4.45 | 4.53 | 4.58 | 4.65 | 4.67 | 4.65 | 4.61 | 4.65 | 4.93 | 5.33 | 5.17 | 5.11 | 5.03 | 4.92 |
| 7 | 5.29 | 5.46 | 5.61 | 5.74 | 5.80 | 5.81 | 5.77 | 5.81 | 6.16 | 6.66 | 6.45 | 6.37 | 6.26 | 6.08 |
| 8 | 6.01 | 6.25 | 6.47 | 6.68 | 6.79 | 6.86 | 6.89 | 6.98 | 7.41 | 8.04 | 7.81 | 7.71 | 7.57 | 7.34 |
| 9 | 6.68 | 7.01 | 7.28 | 7.55 | 7.74 | 7.85 | 7.90 | 7.99 | 8.49 | 9.22 | 9.00 | 8.91 | 8.78 | 8.55 |
| 10 | 7.29 | 7.69 | 8.08 | 8.43 | 8.67 | 8.83 | 8.91 | 9.02 | 9.58 | 10.41 | 10.17 | 10.07 | 9.91 | 9.64 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.171 |
| SC2 | 0 | 8 | 6.975 |
| SC3 | -18 | 7 | 5.767 |
| SC4 | -25 | 6 | 4.583 |
| SC5 | -34 | 6 | 4.471 |
| A | 1357 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1357 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.