EA-330AE7-C05 C
6.87 kW
Defrost: None
Product code: EA-235AC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,911 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 19.1 m² |
| Inner volume | 6.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 48 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-235AC7-C01 C | None |
|---|---|
| EA-235AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.48 | 2.44 | 2.42 | 2.40 | 2.38 | 2.36 | 2.32 | 2.35 | 2.49 | 2.68 | 2.61 | 2.59 | 2.55 | 2.50 |
| 5 | 3.35 | 3.34 | 3.34 | 3.35 | 3.33 | 3.30 | 3.25 | 3.28 | 3.48 | 3.76 | 3.65 | 3.61 | 3.56 | 3.48 |
| 6 | 4.22 | 4.26 | 4.31 | 4.36 | 4.37 | 4.34 | 4.29 | 4.32 | 4.58 | 4.94 | 4.78 | 4.73 | 4.65 | 4.54 |
| 7 | 5.05 | 5.18 | 5.30 | 5.40 | 5.45 | 5.44 | 5.40 | 5.44 | 5.76 | 6.22 | 6.01 | 5.93 | 5.82 | 5.65 |
| 8 | 5.78 | 5.98 | 6.18 | 6.35 | 6.47 | 6.54 | 6.55 | 6.59 | 6.97 | 7.55 | 7.31 | 7.22 | 7.08 | 6.86 |
| 9 | 6.43 | 6.72 | 6.99 | 7.20 | 7.37 | 7.47 | 7.51 | 7.60 | 8.07 | 8.76 | 8.55 | 8.46 | 8.33 | 8.12 |
| 10 | 7.04 | 7.38 | 7.74 | 8.06 | 8.28 | 8.41 | 8.48 | 8.59 | 9.12 | 9.90 | 9.67 | 9.57 | 9.42 | 9.17 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 9.672 |
| SC2 | 0 | 8 | 6.586 |
| SC3 | -18 | 7 | 5.426 |
| SC4 | -25 | 6 | 4.311 |
| SC5 | -34 | 6 | 4.240 |
| A | 1357 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1357 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.