EA-150AC6-C10 C
9.05 kW
Defrost: None
Product code: EA-235AE4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,943 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 45.6 m² |
| Inner volume | 9.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 59 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-235AE4-C01 C | None |
|---|---|
| EA-235AE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.50 | 3.51 | 3.53 | 3.56 | 3.56 | 3.55 | 3.52 | 3.63 | 3.87 | 4.21 | 4.14 | 4.12 | 4.09 | 4.03 |
| 5 | 4.55 | 4.62 | 4.69 | 4.76 | 4.78 | 4.76 | 4.71 | 4.81 | 5.12 | 5.55 | 5.41 | 5.36 | 5.30 | 5.21 |
| 6 | 5.59 | 5.75 | 5.89 | 6.00 | 6.06 | 6.05 | 6.00 | 6.08 | 6.45 | 6.99 | 6.77 | 6.68 | 6.57 | 6.38 |
| 7 | 6.55 | 6.82 | 7.06 | 7.27 | 7.38 | 7.40 | 7.34 | 7.42 | 7.86 | 8.51 | 8.22 | 8.11 | 7.94 | 7.66 |
| 8 | 7.38 | 7.75 | 8.08 | 8.38 | 8.53 | 8.63 | 8.63 | 8.75 | 9.28 | 10.06 | 9.73 | 9.58 | 9.37 | 9.01 |
| 9 | 8.14 | 8.63 | 9.02 | 9.41 | 9.67 | 9.80 | 9.83 | 9.96 | 10.56 | 11.44 | 11.12 | 10.97 | 10.74 | 10.37 |
| 10 | 8.83 | 9.40 | 9.96 | 10.45 | 10.78 | 10.97 | 11.03 | 11.17 | 11.85 | 12.83 | 12.48 | 12.31 | 12.05 | 11.60 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.477 |
| SC2 | 0 | 8 | 8.746 |
| SC3 | -18 | 7 | 7.322 |
| SC4 | -25 | 6 | 5.893 |
| SC5 | -34 | 6 | 5.634 |
| A | 1357 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1357 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.