EA-150AE7-C09 C
10.84 kW
Defrost: None
Product code: EA-240AC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,009 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 39.1 m² |
| Inner volume | 8.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 61 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-240AC4-C01 C | None |
|---|---|
| EA-240AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.09 | 4.00 | 3.96 | 3.95 | 3.93 | 3.90 | 3.87 | 3.97 | 4.20 | 4.56 | 4.47 | 4.44 | 4.40 | 4.34 |
| 5 | 5.52 | 5.44 | 5.40 | 5.39 | 5.35 | 5.30 | 5.23 | 5.33 | 5.66 | 6.13 | 5.99 | 5.94 | 5.88 | 5.79 |
| 6 | 6.99 | 6.97 | 6.97 | 6.98 | 6.94 | 6.87 | 6.77 | 6.85 | 7.26 | 7.85 | 7.62 | 7.55 | 7.44 | 7.30 |
| 7 | 8.48 | 8.54 | 8.61 | 8.66 | 8.65 | 8.58 | 8.46 | 8.51 | 9.01 | 9.72 | 9.39 | 9.27 | 9.11 | 8.86 |
| 8 | 9.84 | 10.01 | 10.20 | 10.38 | 10.43 | 10.38 | 10.25 | 10.29 | 10.88 | 11.74 | 11.32 | 11.15 | 10.92 | 10.56 |
| 9 | 11.04 | 11.32 | 11.59 | 11.85 | 12.00 | 12.03 | 12.00 | 12.10 | 12.82 | 13.84 | 13.35 | 13.15 | 12.86 | 12.40 |
| 10 | 12.17 | 12.59 | 12.93 | 13.27 | 13.47 | 13.56 | 13.56 | 13.66 | 14.48 | 15.67 | 15.24 | 15.05 | 14.77 | 14.31 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.236 |
| SC2 | 0 | 8 | 10.288 |
| SC3 | -18 | 7 | 8.664 |
| SC4 | -25 | 6 | 6.967 |
| SC5 | -34 | 6 | 6.992 |
| A | 1467 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 1467 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.