EA-163ED10-C06 C
9.78 kW
Defrost: None
Product code: EA-240AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,084 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 26.9 m² |
| Inner volume | 12.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 69 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-240AE10-C01 C | None |
|---|---|
| EA-240AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.61 | 3.58 | 3.57 | 3.57 | 3.55 | 3.51 | 3.46 | 3.53 | 3.74 | 4.03 | 3.92 | 3.88 | 3.83 | 3.74 |
| 5 | 4.78 | 4.81 | 4.86 | 4.90 | 4.90 | 4.86 | 4.80 | 4.88 | 5.17 | 5.59 | 5.43 | 5.38 | 5.30 | 5.19 |
| 6 | 5.91 | 6.04 | 6.16 | 6.27 | 6.31 | 6.30 | 6.25 | 6.32 | 6.70 | 7.24 | 7.01 | 6.93 | 6.81 | 6.63 |
| 7 | 7.03 | 7.25 | 7.47 | 7.66 | 7.75 | 7.78 | 7.75 | 7.82 | 8.29 | 8.97 | 8.68 | 8.57 | 8.40 | 8.13 |
| 8 | 8.03 | 8.38 | 8.70 | 9.00 | 9.20 | 9.28 | 9.28 | 9.37 | 9.93 | 10.75 | 10.42 | 10.28 | 10.08 | 9.74 |
| 9 | 8.91 | 9.37 | 9.80 | 10.20 | 10.43 | 10.59 | 10.66 | 10.81 | 11.49 | 12.47 | 12.17 | 12.03 | 11.79 | 11.39 |
| 10 | 9.71 | 10.31 | 10.81 | 11.30 | 11.65 | 11.88 | 11.99 | 12.17 | 12.93 | 14.04 | 13.72 | 13.57 | 13.34 | 12.95 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.723 |
| SC2 | 0 | 8 | 9.366 |
| SC3 | -18 | 7 | 7.710 |
| SC4 | -25 | 6 | 6.159 |
| SC5 | -34 | 6 | 5.944 |
| A | 1467 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1467 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.