EA-530AE8-C01 C
11.54 kW
Defrost: None
Product code: EA-240AE7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,716 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 36.7 m² |
| Inner volume | 12.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 69 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-240AE7-C01 C | None |
|---|---|
| EA-240AE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.39 | 4.35 | 4.34 | 4.34 | 4.32 | 4.28 | 4.23 | 4.35 | 4.64 | 5.02 | 4.91 | 4.87 | 4.81 | 4.72 |
| 5 | 5.79 | 5.81 | 5.86 | 5.90 | 5.89 | 5.85 | 5.77 | 5.88 | 6.24 | 6.76 | 6.57 | 6.51 | 6.44 | 6.33 |
| 6 | 7.15 | 7.28 | 7.40 | 7.51 | 7.55 | 7.52 | 7.44 | 7.52 | 7.98 | 8.62 | 8.34 | 8.24 | 8.10 | 7.88 |
| 7 | 8.49 | 8.74 | 8.96 | 9.16 | 9.24 | 9.25 | 9.18 | 9.26 | 9.80 | 10.60 | 10.24 | 10.10 | 9.89 | 9.55 |
| 8 | 9.70 | 10.06 | 10.41 | 10.73 | 10.93 | 11.01 | 10.96 | 11.04 | 11.69 | 12.64 | 12.22 | 12.04 | 11.78 | 11.36 |
| 9 | 10.76 | 11.27 | 11.74 | 12.16 | 12.37 | 12.53 | 12.57 | 12.72 | 13.49 | 14.62 | 14.23 | 14.04 | 13.73 | 13.21 |
| 10 | 11.74 | 12.41 | 12.96 | 13.50 | 13.84 | 14.05 | 14.13 | 14.30 | 15.17 | 16.44 | 16.02 | 15.82 | 15.52 | 14.99 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.018 |
| SC2 | 0 | 8 | 11.042 |
| SC3 | -18 | 7 | 9.209 |
| SC4 | -25 | 6 | 7.402 |
| SC5 | -34 | 6 | 7.185 |
| A | 1467 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 1467 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.