EA-150AG6-C09 C
12.90 kW
Defrost: None
Product code: EA-240AG4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,620 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 78.1 m² |
| Inner volume | 16.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 93 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-240AG4-C01 C | None |
|---|---|
| EA-240AG4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.11 | 5.21 | 5.30 | 5.40 | 5.44 | 5.43 | 5.39 | 5.58 | 5.96 | 6.49 | 6.37 | 6.33 | 6.29 | 6.24 |
| 5 | 6.45 | 6.66 | 6.85 | 7.01 | 7.10 | 7.11 | 7.06 | 7.21 | 7.67 | 8.33 | 8.10 | 8.01 | 7.89 | 7.71 |
| 6 | 7.76 | 8.10 | 8.40 | 8.64 | 8.79 | 8.84 | 8.79 | 8.92 | 9.47 | 10.27 | 9.93 | 9.80 | 9.60 | 9.28 |
| 7 | 8.93 | 9.43 | 9.88 | 10.27 | 10.50 | 10.59 | 10.55 | 10.68 | 11.32 | 12.26 | 11.86 | 11.69 | 11.42 | not rated |
| 8 | 9.97 | 10.62 | 11.21 | 11.72 | 12.00 | 12.18 | 12.22 | 12.39 | 13.14 | 14.23 | 13.80 | 13.59 | not rated | not rated |
| 9 | 10.91 | 11.73 | 12.38 | 13.05 | 13.50 | 13.75 | 13.83 | 14.02 | 14.86 | 16.09 | 15.64 | 15.41 | not rated | not rated |
| 10 | ≈ 11.75 | 12.76 | 13.59 | 14.40 | 14.97 | 15.30 | 15.44 | 15.65 | 16.60 | 17.96 | 17.46 | 17.21 | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.463 |
| SC2 | 0 | 8 | 12.388 |
| SC3 | -18 | 7 | 10.376 |
| SC4 | -25 | 6 | 8.403 |
| SC5 | -34 | 6 | 7.844 |
| A | 1467 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 1467 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.