EA-245AE7-C01 C
16.85 kW
Defrost: None
Product code: EA-250AC7-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 14,051 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 43.2 m² |
| Inner volume | 14.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 96 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,420 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.4 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-250AC7-C09 C | None |
|---|---|
| EA-250AC7-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.98 | 5.94 | 5.91 | 5.89 | 5.83 | 5.75 | 5.67 | 5.68 | 6.00 | 6.45 | 6.26 | 6.19 | 6.09 | 5.95 |
| 5 | 8.04 | 8.14 | 8.23 | 8.30 | 8.29 | 8.23 | 8.12 | 8.15 | 8.63 | 9.29 | 9.01 | 8.91 | 8.76 | 8.52 |
| 6 | 10.08 | 10.37 | 10.63 | 10.85 | 10.94 | 10.93 | 10.85 | 10.90 | 11.54 | 12.45 | 12.06 | 11.92 | 11.72 | 11.41 |
| 7 | 11.79 | 12.27 | 12.71 | 13.11 | 13.38 | 13.50 | 13.58 | 13.74 | 14.60 | 15.81 | 15.36 | 15.18 | 14.93 | 14.52 |
| 8 | 13.31 | 14.01 | 14.56 | 15.13 | 15.52 | 15.78 | 15.92 | 16.12 | 17.13 | 18.61 | 18.22 | 18.06 | 17.83 | 17.44 |
| 9 | 14.72 | 15.56 | 16.40 | 17.15 | 17.69 | 18.05 | 18.27 | 18.52 | 19.69 | 21.41 | 20.98 | 20.80 | 20.53 | 20.08 |
| 10 | 15.92 | 17.08 | 18.15 | 19.12 | 19.83 | 20.32 | 20.63 | 20.94 | 22.28 | 24.24 | 23.78 | 23.58 | 23.28 | 22.76 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 23.783 |
| SC2 | 0 | 8 | 16.116 |
| SC3 | -18 | 7 | 13.230 |
| SC4 | -25 | 6 | 10.631 |
| SC5 | -34 | 6 | 10.153 |
| A | 2087 mm |
|---|---|
| B | 590 mm |
| C | 685 mm |
| F | 395 mm |
| E1 | 868 mm |
| E | 1735 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2087 mm |
|---|---|
| Width | 590 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.